Parameter Details
11
11.6 E: Motor Parameters
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 645
■ E3-06: Motor 2 Base Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-06
(031C)
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
■ E3-07: Motor 2 Mid Point A Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-07
(031D)
Motor 2 Mid Point A
Frequency
Sets a middle output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
■ E3-08: Motor 2 Mid Point A Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-08
(031E)
Motor 2 Mid Point A
Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■ E3-09: Motor 2 Minimum Output Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-09
(031F)
Motor 2 Minimum Output
Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
■ E3-10: Motor 2 Minimum Output Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-10
(0320)
Motor 2 Minimum Output
Voltage
Sets the minimum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
■ E3-11: Motor 2 Mid Point B Frequency
No.
(Hex.)
Name Description
Default
(Range)
E3-11
(0345)
Expert
Motor 2 Mid Point B
Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 Hz
(0.0 - E3-04)
Note:
• Set this parameter to 0.0 to disable the function.
• When you initialize the drive, this parameter is reset to the default value.
■ E3-12: Motor 2 Mid Point B Voltage
No.
(Hex.)
Name Description
Default
(Range)
E3-12
(0346)
Expert
Motor 2 Mid Point B
Voltage
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this parameter.
0.0 V
(200 V Class: 0.0 to 255.0
V, 400 V Class: 0.0 to 510.0
V)
Note:
• Set this parameter to 0.0 to disable the function.
• When you initialize the drive, this parameter is reset to the default value.
• The setting value changes automatically when you do Auto-Tuning (rotational and stationary 1 or 2).