4.3 UL Standards
292 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC will turn ON, and
MB-MC will turn OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF.
3 : Alarm Only
oH3 appears on the keypad, and operation continues. The output terminal set for Alarm [H2-01 to H2-05 = 10]
switches ON.
L1-04: Motor Thermistor oH Fault Select
No.
(Hex.)
Name Description
Default
(Range)
L1-04
(0483)
Motor Thermistor oH Fault
Select
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor Overheat
Fault (PTC Input)] detection level.
1
(0 - 2)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and
MB-MC turns OFF.
1 : Coast to Stop
The output turns OFF and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC
turns OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-
MC turns ON, and MB-MC turns OFF.
V/f
CL-V/f
OLV
CLV
AOLV