Specifications
9
9.4 Drive Specifications
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 435
Item Specification
Overload Protection
Drive stops when the output current is more than 150% of the rated output current for 60 s.
Note:
The drive may trigger the overload protection function at 150% of the drive rated output in under 60 s if the output frequency is less than 6 Hz.
Overvoltage
Protection
200 V class: Stops when the DC bus voltage is more than approximately 410 V
400 V class: Stops when the DC bus voltage is more than approximately 820 V
Undervoltage
Protection
200 V class: Stops when the DC bus voltage decreases to less than approximately 190 V
400 V class: Stops when the DC bus voltage decreases to less than approximately 380 V
Heatsink Overheat
Protection
Thermistor
Braking Resistor
Overheat Protection
Overheat detection for braking resistor (optional ERF-type, 3% ED)
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects any ground faults during run. The drive will not provide protection when:
There is a low-resistance ground fault for the motor cable or terminal block
Energizing the drive when there is a ground fault present.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is above 50 V.
Table 9.8 Environment
Environment
Conditions
Area of Use
Indoors
Noxious Fumes: IEC60721-3-3:3C2
Dust: IEC60721-3-3:3S2
Power Supply
Overvoltage Category III
Ambient
Temperature
Open chassis type (IP20): -10°C to +50 °C (14 °F to 122 °F)
Enclosed wall-mounted type (UL Type 1): -10 °C to +40 °C (14 °F to 104 °F)
Do not use the drive in a location where the temperature changes suddenly to improve the drive reliability.
When installing the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
Do not let the drive freeze.
Derate the output current and output voltage to install the drive in areas with ambient temperatures 60 °C (140 °F).
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
Oil mist, corrosive or flammable gas, or dust
Metal powder, oil, water, or other unwanted materials
Radioactive materials or flammable materials, including wood
Harmful gas or fluids
Salt
Direct sunlight
Keep wood or other flammable materials away from the drive.
Altitude
1000 m (3281 ft.) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft.) to install the drive in altitudes between 1000 m to 4000 m (3281 ft. to 13123 ft.).
It is not necessary to derate the rated voltage in these conditions:
Installing the drive at 2000 m (6562 ft.) or lower
Installing the drive between 2000 m to 4000 m (6562 ft. to 13123 ft.) and grounding the neutral point on the power supply.
Contact Yaskawa or your nearest sales representative when not grounding the neutral point.
Vibration
10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
20 Hz to 55 Hz:
2003 to 2180, 4002 to 4150: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
2215 to 2415, 4180 to 4605: 0.2 G (2.0 m/s
2
, 6.56 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient cooling airflow.