Parameter List
10
10.9 F: Options
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 497
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-35
(0377)
Dynamic In Param 3 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined. When you use a ProfiNet option, set this parameter to set to configurable
input 3.
0
682
F7-36
(0378)
Dynamic In Param 4 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined. When you use a ProfiNet option, set this parameter to set to configurable
input 4.
0
682
F7-37
(0379)
Dynamic In Param 5 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined. When you use a ProfiNet option, set this parameter to set to configurable
input 5.
0
682
F7-38
(037A)
Dynamic In Param 6 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined.
0
682
F7-39
(037B)
Dynamic In Param 7 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined.
0
682
F7-40
(037C)
Dynamic In Param 8 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined.
0
682
F7-41
(037D)
Dynamic In Param 9 for
CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined.
0
682
F7-42
(037E)
Dynamic In Param 10
for CommCard
Sets Input Assembly 166 when you use an Ethernet/IP option. The drive sends the
values from the MEMOBUS/Modbus address registers stored for each parameter to
Input Assembly 166. The drive returns the default register value for the option card
when the MEMOBUS/Modbus address is 0 and the value sent to Input Assembly 166 is
not defined.
0
682
F7-60
(0780)
PZD1 Write (Control
Word)
When you use a Profibus option, set the MEMOBUS/Modbus address for PZD1 (PPO
output). PZD1 (PPO output) functions as the STW when F7-60 = 0 to 2.
0
683
F7-61
(0781)
PZD2 Write (Frequency
Reference)
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD2 (PPO
output). PZD2 (PPO output) functions as the HSW when F7-61 = 0 to 2.
0
683
F7-62
(0782)
PZD3 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD3 (PPO
output). A value of 0, 1, or 2 will disable the PZD3 (PPO output) write operation to the
MEMOBUS/Modbus register.
0
683
F7-63
(0783)
PZD4 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD4 (PPO
output). A value of 0, 1, or 2 will disable the PZD4 (PPO output) write operation to the
MEMOBUS/Modbus register.
0
683
F7-64
(0784)
PZD5 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD5 (PPO
output). A value of 0, 1, or 2 will disable the PZD5 (PPO output) write operation to the
MEMOBUS/Modbus register.
0
683
F7-65
(0785)
PZD6 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD6 (PPO
output). A value of 0, 1, or 2 will disable the PZD6 (PPO output) write operation to the
MEMOBUS/Modbus register.
0
683
F7-66
(0786)
PZD7 Write
When you use a Profibus option, sets the MEMOBUS/Modbus address for PZD7 (PPO
output). A value of 0, 1, or 2 will disable the PZD7 (PPO output) write operation to the
MEMOBUS/Modbus register.
0
683
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV