10.20 Parameters Changed by o2-04 [Drive Model (KVA) Selection]
566 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No. Name Unit Default
- Drive Model - 4150 4180 4216 4260
o2-04
Drive Model (KVA)
Selection
Hex. A5 A6 A7 A8
Motor 1: E2-11
Motor 2: E4-11
Motor 3: E7-31
Motor Rated Power kW 75 90 110 132
n2-01
Automatic Freq
Regulator Gain(F)
- 1.00 1.00 1.00 1.00
n5-02
Motor Inertia
Acceleration Time
s 0.533 0.592 0.646 0.673
No. Name Unit Default
- Drive Model - 4304 4371 4414 4453
o2-04
Drive Model (KVA)
Selection
Hex. A9 AA AC AD
Motor 1: E2-11
Motor 2: E4-11
Motor 3: E7-31
Motor Rated Power kW 160 200 220 250
Motor 1: C5-17
Motor 2: C5-37
Motor Inertia kgm
2
3.30 3.60 4.10 6.50
C6-02
Carrier Frequency
Selection
- 1 1 1 1
E1-01
Input AC Supply
Voltage
V 400 400 400 400
Motor 1: E2-01
Motor 2: E4-01
Motor 3: E7-21
Motor Rated Current
(FLA)
A 270 310 370 500
Motor 1: E2-02
Motor 2: E4-02
Motor Rated Slip Hz 1.35 1.3 1.3 1.25
Motor 1: E2-03
Motor 2: E4-03
Motor No-Load
Current
A 70 81 96 130
Motor 1: E2-05
Motor 2: E4-05
Motor 3: E7-25
Motor Line-to-Line
Resistance
Ω 0.029 0.025 0.02 0.014
Motor 1: E2-06
Motor 2: E4-06
Motor Leakage
Inductance
% 20 20 20 20
Motor 1: E2-10
Motor 2: E4-10
Motor Iron Loss W 2850 3200 3700 4700
L2-03
Minimum Baseblock
Time
s 1.8 1.9 2 2.1
L2-05
Undervoltage Detection
Lvl (Uv1)
- 380 380 380 380
L3-24
Motor Accel Time @
Rated Torque
s 0.777 0.864 0.91 1.392
L8-02 Overheat Alarm Level °C 130 140 140 140
L8-09
Output Ground Fault
Detection
- 1 1 1 1
L8-38
Carrier Frequency
Reduction
- 2 2 2 2
L8-39
Carrier Freq Reduction
during oL
- 2 2 2 2
n1-01
Hunting Prevention
Selection
- 2 2 2 2
n1-03
Hunting Prevention
Time Constant
ms 30 100 100 100
n1-16
Hunting Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50
n2-01
Automatic Freq
Regulator Gain(F)
- 1.00 1.00 1.00 1.00
n5-02
Motor Inertia
Acceleration Time
s 0.777 0.864 0.91 1.392