Parameter Details
11
11.2 A: Initialization Parameters
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 573
Table 11.1 Parameters Saved as User Parameters with the General Preset
User Parameter No.
Parameter No. Saved
Name
A2-01 A1-02
Control Method Selection
A2-02 b1-01
Frequency Reference Selection 1
A2-03 b1-02
Run Command Selection 1
A2-04 b1-03
Stopping Method Selection
A2-05 C1-01
Acceleration Time 1
A2-06 C1-02
Deceleration Time 1
A2-07 C6-02
Carrier Frequency Selection
A2-08 d1-01
Reference 1
A2-09 d1-02
Reference 2
A2-10 d1-03
Reference 3
A2-11 d1-04
Reference 4
A2-12 d1-17
Jog Reference
A2-13 E1-01
Input AC Supply Voltage
A2-14 E1-03
V/f Pattern Selection
A2-15 E1-04
Maximum Output Frequency
A2-16 E1-05
Maximum Output Voltage
A2-17 E1-06
Base Frequency
A2-18 E1-09
Minimum Output Frequency
A2-19 E1-13
Base Voltage
A2-20 E2-01
Motor Rated Current (FLA)
A2-21 E2-04
Motor Pole Count
A2-22 E2-11
Motor Rated Power
A2-23 H4-02
Terminal FM Analog Output Gain
A2-24 L1-01
Motor Overload (oL1) Protection
A2-25 L3-04
Stall Prevention during Decel
1 : Crane (Hoist)
The drive automatically sets these parameters for a hoist application.
Note:
Make sure that you do Auto-Tuning after you set A1-06 for a hoist application. Refer to
Notes when Opening and Closing the Brake
Without the Crane Sequence on page 577
for hoist (elevator) instructions.
Table 11.2 Best Parameter Settings for Hoist Applications
No. Name Optimal Value
A1-02 Control Method Selection 2: Open Loop Vector
b1-01 Frequency Reference Selection 1 0: Keypad
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C1-09 Fast Stop Time 2.0 s
d1-01 Reference 1 5.00 Hz
d1-02 Reference 2 25.00 Hz
d1-03 Reference 3 50.00 Hz
E1-03 V/f Pattern Selection F: Custom
H2-01 Term M1-M2 Function Selection 21: Brake Release Command
H2-02 Term M3-M4 Function Selection 1: Zero Speed
H3-06 Terminal A3 Function Selection F: Not Used (Through Mode)
L2-03 Minimum Baseblock Time 0.1 s