Parameter Details
11
11.4 C: Tuning
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 619
C5-28: Motor 2 ASR Integral Limit
No.
(Hex.)
Name Description
Default
(Range)
C5-28
(035D)
Motor 2 ASR Integral Limit
Set the upper limit of the motor 2 ASR integral amount as a percentage of the rated load.
400%
(0 - 400%)
C5-29: Speed Control Response
No.
(Hex.)
Name Description
Default
(Range)
C5-29
(0B18)
Expert
Speed Control Response
Sets the level of speed control responsiveness. Usually it is not necessary to change this setting.
0
(0, 1)
If a high level of speed control responsiveness is necessary, set C5-29 = 1,then adjust the speed control (ASR)
parameter.
0 : Standard
1 : High Performance 1
C5-32: Motor 2 Integral Oper at Acc/Dec
No.
(Hex.)
Name Description
Default
(Range)
C5-32
(0361)
Motor 2 Integral Oper at
Acc/Dec
Sets ASR integral operation during acceleration and deceleration for motor 2.
0
(0, 1)
When it is necessary for the motor speed to be as near the frequency reference as possible during acceleration or
deceleration, set this parameter to 1.
Note:
If you enable integral control, overshoot or undershoot can occur when acceleration or deceleration complete. If there are problems with
overshooting and undershooting, set this parameter to 0.
0 : Disabled
Integral operation is not enabled during acceleration or deceleration. Integral operation is always enabled during
constant speed.
1 : Enabled
Integral operation is always enabled.
C5-37: Motor 2 Inertia
No.
(Hex.)
Name Description
Default
(Range)
C5-37
(0278)
Expert
Motor 2 Inertia
Sets the motor inertia.
Determined by o2-04
(0.0001 - 6.0000 kgm
2
)
Automatically sets C5-37 with the value of [Motor Inertia] when executing any of the following Auto-Tuning
processes.
Inertia Tuning
ASR Tuning
C5-38: Motor 2 Load Inertia Ratio
No.
(Hex.)
Name Description
Default
(Range)
C5-38
(0279)
Expert
Motor 2 Load Inertia Ratio
Sets the load inertia ratio for the motor 2 inertia.
1.0
(0.0 - 6000.0)
The drive automatically sets C5-38 to the value of [Load Inertia Ratio] when you do Inertia Tuning or ASR
Tuning.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV