Parameter Details
11
11.5 d: References
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 625
■ d1-03: Reference 3
No.
(Hex.)
Name Description
Default
(Range)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• To set d1-03 to Multi-Step Speed 3, set H3-02, H3-06, and H3-10 ≠ 3 [MFAI Function Selection ≠ Auxiliary Frequency Reference 2].
■ d1-04: Reference 4
No.
(Hex.)
Name Description
Default
(Range)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• Parameter d1-04 sets the frequency reference of Multi-Step Speed 4.
■ d1-05: Reference 5
No.
(Hex.)
Name Description
Default
(Range)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• Parameter d1-05 sets the frequency reference of Multi-Step Speed 5.
■ d1-06: Reference 6
No.
(Hex.)
Name Description
Default
(Range)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• Parameter d1-06 sets the frequency reference of Multi-Step Speed 6.
■ d1-07: Reference 7
No.
(Hex.)
Name Description
Default
(Range)
d1-07
(0286)
RUN
Reference 7
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• Parameter d1-07 sets the frequency reference of Multi-Step Speed 7.