11.6 E: Motor Parameters
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 647
The value set for E4-01 becomes the reference value for motor protection and the torque limit. Enter the motor
rated current as shown on the motor nameplate. The value of E4-01 is automatically set to the value input for
[Motor Rated Current] by the Auto-Tuning process.
E4-02: Motor 2 Rated Slip
No.
(Hex.)
Name Description
Default
(Range)
E4-02
(0322)
Motor 2 Rated Slip
Sets the motor rated slip for motor 2.
Determined by o2-04
(0.000 - 20.000 Hz)
The setting value of E4-02 is the slip compensation reference value. The drive sets this parameter during the
Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning). If Auto-Tuning cannot be performed,
calculate the motor rated slip using the information written on the motor nameplate and the formula below:
E4-02 = f - (n × p) / 120
f: Motor rated frequency (Hz)
n: Rated motor speed (min
-1
(r/min))
p: Number of motor poles
E4-03: Motor 2 Rated No-Load Current
No.
(Hex.)
Name Description
Default
(Range)
E4-03
(0323)
Motor 2 Rated No-Load
Current
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-
load voltage.
Determined by o2-04
(Less than 0 - E4-01)
Note:
The default settings and setting ranges appear in the following units:
2003 to 2033, 4002 to 4018: 0.01 A units
2047 to 2415, 4024 to 4605: 0.1 A units
The drive sets this parameter during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-
Tuning). The motor no-load current listed in the motor test report can also be entered to E2-03 manually. Contact
the motor manufacturer to receive a copy of the motor test report.
Note:
The default setting of the no-load current is for performance with a 4-pole motor recommended by Yaskawa.
E4-04: Motor 2 Motor Poles
No.
(Hex.)
Name Description
Default
(Range)
E4-04
(0324)
Motor 2 Motor Poles
Sets the number of poles for motor 2.
4
(2 - 120)
Auto-Tuning automatically sets E4-04 to the value input for [Number of Motor Poles].
E4-05: Motor 2 Line-to-Line Resistance
No.
(Hex.)
Name Description
Default
(Range)
E4-05
(0325)
Motor 2 Line-to-Line
Resistance
Sets the line-to-line resistance for the motor 2 stator windings.
Determined by o2-04
(0.000 - 65.000 Ω)
Note:
This value represents the line-to-line resistance for motor 2. Be careful not to set this parameter with the single phase resistance.
If Auto-Tuning completes successfully, this value is automatically calculated. If Auto-Tuning cannot be executed,
obtain a test report from the motor manufacturer. Use the information found on the motor nameplate with any of
the following formulas to calculate the motor line-to-line resistance.
E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV