Parameter Details
11
11.7 F: Options
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 663
Terminal V1 will output an analog signal = 100% of the parameter set in F4-01.
4. View the monitor connected to terminal V1 and adjust F4-05.
• Use Gain and Bias to Adjust the Output Signal Level of Terminal V2
You must stop the drive to adjust the output signal. Use this procedure to calibrate the drive:
1. View the F4-04 [Terminal V2 Gain] value on the keypad.
Terminal V2 will output a voltage = 100% of the monitor set in F4-03 [Terminal V2 Function Selection].
2. View the monitor connected to terminal V2 and adjust F4-04.
3. View the F4-06 [Terminal V2 Bias] value on the keypad.
The analog signal equal to 0% of the parameter being set in F4-03 will be output from terminal V2.
4. View the monitor connected to terminal V2 and adjust F4-06.
■ F4-01: Terminal V1 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F4-01
(0391)
Terminal V1 Function
Selection
Sets the monitor signal output from terminal V1.
102
(000 - 999)
Set the x-xx part of the Ux-xx [Monitors] to set monitor data to output from the option card. For example, set F4-
01 = 102 to monitor U1-02 [Output Frequency].
Note:
• You cannot use all of the monitors in all of the control methods.
• When you use the terminal in through mode, set this parameter to 000 or 031. You can use MEMOBUS/Modbus communications or
the communication option to set the terminal V1 output level from the PLC.
■ F4-02: Terminal V1 Gain
No.
(Hex.)
Name Description
Default
(Range)
F4-02
(0392)
RUN
Terminal V1 Gain
Sets the gain of the monitor signal that is sent from terminal V1. Sets the analog signal output
level from the terminal V1 at 10 V or 20 mA as 100% when an output for monitoring items is
100%.
100.0%
(-999.9 - +999.9%)
The maximum output voltage output from terminal V1 is ±10 V. Use F4-07 [Terminal V1 Signal Level] to set the
signal level.
Example settings:
When you use these settings, and the monitored output voltage is at 100% (drive rated current), the output voltage
of terminal V1 is 5 V (50% of 10 V). The output current is 200% of the drive rated current when terminal V1
outputs a maximum voltage of 10 V.
• F4-01 [Terminal V1 Function Selection] = 102 (U1-02: Output Frequency)
• F4-02 = 50.0%
• F4-05 [Terminal V1 Bias] = 0.0%
• F4-07 = 0 (0 V to 10 V)
■ F4-03: Terminal V2 Function Selection
No.
(Hex.)
Name Description
Default
(Range)
F4-03
(0393)
Terminal V2 Function
Selection
Sets the monitor signal output from terminal V2.
103
(000 - 999)
Set the x-xx part of the Ux-xx [Monitors] to set monitor data to output from the option card. For example, set F4-
03 = 103 to monitor U1-03 [Output Current].
Note:
• You cannot use all of the monitors in all of the control methods.
• When you use the terminal in through mode, set this parameter to 000 or 031. You can use this setting to adjust the V2 terminal output
from PLC through MEMOBUS/Modbus communications or a communications option.