11.7 F: Options
670 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
The multi-step speed reference (2-step speed to 8-step speed references) and the Jog Frequency Reference (JOG
command) are disabled when NetRef or ComRef is selected as the frequency reference source.
1 : Enable Multi-Step References
The multi-step speed reference (2-step speed through 8-step speed references) and the Jog Frequency Reference
(JOG command) are enabled, and the frequency reference can be changed when NetRef or ComRef is selected as
the frequency reference source.
F6-08: Comm Parameter Reset @Initialize
No.
(Hex.)
Name Description
Default
(Range)
F6-08
(036A)
Comm Parameter Reset
@Initialize
Sets the function to initialize F6-xx and F7-xx parameters when the drive is initialized with A1-03
[Initialize Parameters].
0
(0, 1)
0 : No Reset - Parameters Retained
1 : Reset Back to Factory Default
Note:
When you use A1-03 to initialize the drive, this setting will not change.
F6-10: CC-Link Node Address
No.
(Hex.)
Name Description
Default
(Range)
F6-10
(03B6)
CC-Link Node Address
Sets the node address for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 64)
Note:
Be sure to set a node address that is different than all other node addresses. Do not set this parameter to 0. Incorrect parameter settings
will cause AEr [Station Address Setting Error] errors and the L.ERR LED on the option will come on.
When the only drive is connected, you can connect a maximum of 42 nodes. Follow these rules to connect devices
that are not drives:
{(1 × a) + (2 × b) + (3 × c) + (4 × d)} 64
(a: number of units that occupies 1 node, b: number of units that occupies 2 nodes, c: number of units that
occupies 3 nodes, d: number of units that occupies 4 nodes)
{(16 × A) + (54 × B) + (88 × C)} 2304
(A: number of remote I/O nodes (64 max.), B: number of remote device nodes (42 max.), C: number of local
nodes (26 max.))
F6-11: CC-Link Communication Speed
No.
(Hex.)
Name Description
Default
(Range)
F6-11
(03B7)
CC-Link Communication
Speed
Sets the communication speed for CC-Link communication. Restart the drive after you change the
parameter setting.
0
(0 - 4)
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
F6-14: BUS Error Auto Reset
No.
(Hex.)
Name Description
Default
(Range)
F6-14
(03BB)
BUS Error Auto Reset
Sets the automatic reset function for bUS [Option Communication Errors].
0
(0, 1)
0 : Disable
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV