11.8 H: Terminal Functions
740 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
H5-17: ENTER command response @CPU BUSY
No.
(Hex.)
Name Description
Default
(Range)
H5-17
(11A1)
Expert
ENTER command response
@CPU BUSY
Sets operation when the EEPROM write command is sent without EEPROM write available.
Usually it is not necessary to change this setting.
0
(0, 1)
0 : Ignore Command(No ROM/RAM Write)
1 : Write to RAM Only
H5-18: Motor Speed Filter over Comms
No.
(Hex.)
Name Description
Default
(Range)
H5-18
(11A2)
Motor Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
0 ms
(0 - 100 ms)
Sets the filter time constant when you monitor the output frequency or motor speed during MEMOBUS/Modbus
communications or use of the communication option.
These are the MEMOBUS registers:
003EH (Output Frequency)
003FH (Output Frequency)
0044H (U1-05: Motor Speed)
00ACH (U1-05: Motor Speed)
00ADH (U1-05: Motor Speed)
H5-20: Communication Parameters Reload
No.
(Hex.)
Name Description
Default
(Range)
H5-20
(0B57)
Communication Parameters
Reload
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0
(0, 1)
0 : Reload at Next Power Cycle
1 : Reload Now
Note:
The setting value automatically returns to H5-20 = 0 after you enable MEMOBUS/Modbus communications parameter changes.
The setting values of these parameters are enabled:
H5-01 [Drive Node Address]
H5-02 [Communication Speed Selection]
H5-03 [Communication Parity Selection]
H5-06 [Drive Transmit Wait Time]
H5-25: Function 5A Register 1 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-25
(1589)
RUN
Function 5A Register 1
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26: Function 5A Register 2 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-26
(158A)
RUN
Function 5A Register 2
Selection
Returns the contents of the specified MEMOBUS/Modbus communications register when
responding to the master device.
0045H (U1-06)
(0000H - FFFFH)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV