11.9 L: Protection Function
752 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Figure 11.90 Current Limit Method
L3-02: Stall Prevent Level during Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-02
(0490)
Stall Prevent Level during
Accel
Sets the output current level as a percentage of the drive rated output current that the drive uses
when the Stall Prevention function is enabled during acceleration.
Determined by L8-38
(0 - 150%)
Note:
The upper limit of this setting is determined by L8-38 [Carrier Frequency Reduction].
Motors may stall if continuing to operate at default settings when motor output is small relative to drive capacity. Decrease the setting
value if stalls occur.
When you operate the motor in the constant power range, set L3-03 [Stall Prevent Limit during Accel].
L3-03: Stall Prevent Limit during Accel
No.
(Hex.)
Name Description
Default
(Range)
L3-03
(0491)
Stall Prevent Limit during
Accel
Sets the lower limit for the stall prevention level used in the constant output range as a percentage
of the drive rated output current.
50%
(0 - 100%)
The stall prevention level set in L3-02 [Stall Prevent Level during Accel] is automatically reduced when the motor
is running within the constant output range. Parameter L3-03 is the limit value used to prevent the stall prevention
level during constant output ranges to fall below the minimum required level.
Note:
The function to automatically reduce the stall prevention level does not operate when L3-01 = 3 [Stall Prevention during Accel =
Current Limit Method].
Figure 11.91 Stall Prevent Level during Accel/Limit
L3-04: Stall Prevention during Decel
No.
(Hex.)
Name Description
Default
(Range)
L3-04
(0492)
Stall Prevention during
Decel
Sets the method that the drive will use to prevent overvoltage faults when it decelerates.
0
(0 - 5)
Note:
To connect a dynamic braking option (braking resistor or braking resistor unit) to the drive, set this parameter to 0 or 3. If this parameter
is set to a value other than 0 or 3, then the Stall Prevention function during deceleration will be enabled, and the dynamic braking option
will not function.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV