Parameter Details
11
11.11 o: Keypad-Related Settings
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 789
Deletes all of the saved user parameter setting values.
Set o2-03 = 2 then push to clear the user parameter setting values. The drive will automatically reset o2-03 to
0. If you delete the user parameter setting values, you cannot set A1-03 = 1110 to initialize parameters.
■ o2-04: Drive Model (KVA) Selection
No.
(Hex.)
Name Description
Default
(Range)
o2-04
(0508)
Drive Model (KVA)
Selection
Sets the Drive Model code. Set this parameter after replacing the control board.
Determined by the drive
(-)
NOTICE: Set o2-04 [Drive Model (KVA) Selection] correctly. If you set this parameter incorrectly, it will decrease drive
performance, cause the protection function to operate incorrectly, and cause damage to the drive.
Note:
When the setting value of o2-04 changes, related parameter setting values also change. Refer to
Parameters Changed by o2-04 [Drive
Model (KVA) Selection] on page 557
for more information.
These tables list the relation between o2-04 setting values and drive models.
■ o2-05: Home Mode Freq Ref Entry Mode
No.
(Hex.)
Name Description
Default
(Setting Range)
o2-05
(0509)
Home Mode Freq Ref Entry
Mode
Sets the function that makes it necessary to push to use the keypad to change the frequency
reference value while in Drive Mode.
0
(0, 1)
0 : ENTER Key Required
You must push to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is
not necessary to push . The drive keeps the frequency reference for 5 seconds after you use and on
the keypad to change the frequency reference value.
■ o2-06: Keypad Disconnect Detection
No.
(Hex.)
Name Description
Default
(Range)
o2-06
(050A)
Keypad Disconnect
Detection
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive
or if you damage the cable while the keypad is the Run command source.
0
(0, 1)
This parameter operates even when the keypad installed to the drive becomes disconnected. This parameter is
enabled in the following circumstances.
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• Using Local mode
0 : Disabled
The drive continues to operate even when a keypad disconnection is detected.
1 : Enabled
Once a keypad disconnection is detected, the drive stops operating and the oPr [Keypad Connection Fault]
indicator appears. The motor coasts to stop.
■ o2-07: Keypad RUN Direction @ Power-up
No.
(Hex.)
Name Description
Default
(Range)
o2-07
(0527)
Keypad RUN Direction @
Power-up
Sets the direction of motor rotation when the drive is energized and the keypad is the Run
command source.
0
(0, 1)
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]