Enabling and Disabling Load Share and Other Functions
When a drive is selected as the slave with Load Share Function select (SA-01 = 2), the
following functions are disabled. To use these functions, set them on the master side.
Setting Value
of H1-
Function
Setting Value
of H1-
Function
3H Multi-Step Speed Reference 1 12H Forward Jog
4H Multi-Step Speed Reference 2 13H Reverse Jog
5H Multi-Step Speed Reference 3 1EH Analog Frequency Reference Sampling/Hold
6H Jog Frequency Selection 32H Multi-Step Speed Reference 4
AH Acceleration/Deceleration Ramp Hold 44H Add Offset Frequency 1
CH Analog Terminal Enable Selection 45H Add Offset Frequency 2
10H Up Command 46H Add Offset Frequency 3
11H Down Command
When a drive is selected as the slave with Load Share Function select (SA-01 = 2), the
following functions are disabled. To use these functions, set them on the master side.
Parameter Name Parameter Name
C2 S-Curve Time Setting D4 UP/DOWN
D1 Multi-Step Speed D7 Offset Frequency
D3 Jump Frequency L3
Stall Prevention during Acceleration and
Deceleration
* When Load Share is enabled, Proportional & Integral Control (L7-07 = 1) and Proportional
Only (L7-07 = 0) are invalid as the setting of L7-07 (Torque Limit during Accel/Decel).
Load Share is disabled when the following references are input. Ensure that the following
references are simultaneously input to the master and slave.
Setting Value
of H1-
Function
Setting Value
of H1-
Function
15H Fast Stop (N.O.) 20H to 2FH External Fault
17H Fast Stop (N.C.)
• The following functions are executed with a higher priority than Load Share.
Parameter Name Parameter Name
- Jog Operation (Keypad Input) T1 Auto-Tuning
Slave Reverse Run Specifications
The direction of the output rotation speed of the slave is dependent on the polarity of the
frequency reference voltage that was input. It is not dependent on the direction of the Run
command (Forward/Reverse).
The direction of the output frequency is as follows.
If the input frequency reference signal is + (positive), the output frequency is positive.
If the input frequency reference signal is - (negative), the output frequency is negative.
* Excluding Auto-Tuning, Jog Operation, and LOCAL Mode.