DONE ERROR STATUS Description
1 0 0000h Job executed without error
0 0 0000h No job executing
0 0 8181h Job active, the block call is to be repeated with the same parameters until
DONE or ERROR is returned.
0 1 8183h There is no CP configuration for this job or the service has not yet started
in the Ethernet-CP 343.
0 1 8186h Parameter ID is invalid. The permitted ID depends on the selected com-
mand.
0 1 8187h Parameter CMD is invalid
0 1 8188h Sequence error in the ACT control
0 1 8090h Module with this address does not exist or CPU in STOP.
0 1 8091h The module base address is not on a double-word boundary.
0 1 80B0h The module does not recognize the record set.
0 1 80C0h The record set cannot be read.
0 1 80C1h The specified record set is currently being processed.
0 1 80C2h There are too many jobs pending.
0 1 80C3h CPU resources (memory) occupied.
0 1 80C4h Communication error (error occurs temporarily; it is usually best to repeat
the job in the user program).
0 1 80D2h The module base address is incorrect.
The output parameters are set to the following values during a restart of the CP:
n DONE = 0
n NDR = 0
n ERROR = 8180h (at AG_RECV)
n ERROR = 8181h (at AG_SEND)
Please consider the block may only be called with new parameters if a
job started before was just ended with DONE = 1.
The following table shows the possible commands and the results that may be evaluated
in the parameters RESULT1 and RESULT2.
NOP - no operation
The block is executed without a job being sent to the CP.
RESULT Hex value/range Description
RESULT 1 0000 0001h Executed without error
RESULT 2 0000 0000h Default
Status parameter at cold
restart
Commands and evaluating
the job results
CMD 0
VIPA SPEED7
Network Communication
Ethernet Communication > FC 10 - AG_CNTRL - Control CP 343
HB00 | OPL_SP7 | Operation list | en | 18-30 147