DCF Electrical Data - Regular Quiet
ELECTRICAL DATA 1 2 3
Unit Data DCF046DR-07DXY0 DCF048DR-07DPY0 DCF051DR-08DPV0
Nominal Run Amps (1) A 292.9 303.4 331.7
Maximum Start Amps A 568.5 566.8 595.1
Recommended Mains Fuse Size A 315 355 355
Evaporator
Immersion Heater Rating W 170 170 170
Condenser Fan - Per Fan (EC)
Quantity 7 7 8
Full Load Amps A 3.9 3.9 3.9
Motor Rating kW 2.6 2.6 2.6
Compressor - Per Compressor
Nominal Run Amps A 36 / 47.9 59.2 / 47.9 59.2 / 55.2
Quantity 3 + 3 2 + 3 2 + 3
Motor Rating kW 22.7 / 29.8 36.2 / 29.8 36.2 / 33.1
Sump Heater Rating W 140 140 140
Start Amps (2) A 210 / 326 298 / 326 298 / 326
OPTIONAL EXTRAS
Power Factor Correction (PF 0.98) (3)
Nominal Run Amps A 281.1 287.2 308.4
Reactive power reduction/saving (4) kVAr 22.6 29.8 41.1
Maximum Start Amps A 556.7 550.6 571.8
Recommended Mains Fuse Size A 315 355 355
Electronic Soft-start
Nominal Run Amps A 292.9 303.4 331.7
Maximum Start Amps A 438.1 436.4 464.7
Recommended Mains Fuse A 315 355 355
Power Factor Correction (PF
0.98) & Electronic Soft Start (3)
Nominal Run Amps A 281.1 287.2 308.4
Maximum Start Amps A 426.3 420.2 441.4
Recommended Mains Fuse Size A 315.0 355.0 355.0
Standard Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 14.8 14.8 14.8
Unit Nominal Run Amps A 307.5 318.0 346.4
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 8.4 8.4 8.4
Larger Head Pump (Single
or Run/Standby)
Pump Full Load Amps A 28.5 28.5 28.5
Unit Nominal Run Amps A 321.1 331.7 360.1
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 16.4 16.4 16.4
Standard Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 13.9 13.9 13.9
Unit Nominal Run Amps A 304.3 314.7 342.8
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 8.6 8.6 8.6
Larger Head Inverter Pump
(Single or Run/Standby)
Pump Full Load Amps A 26.9 26.9 26.9
Unit Nominal Run Amps A 315.2 325.4 353.3
Recommended Mains Fuse Size A 355 355 400
Motor Rating kW 16.8 16.8 16.8
(1) Based upon 7.2°C Evap / 54.4°C Condensing, AC Fans.
(2) Starting amps refers to the direct online connections.
(3) For unit RLA values at alternative power factor values contact Airedale.
(4) Projected reactive power reduction based on a 0.95PF billing threshold.