Notes: Units DCF061DX-16DVV0 DCF066DX-16FVW0 DCF069DX-16FWW0
SEPR
1,3,5 6.72 6.72 6.62
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 618005 662441 705943
Rated Refrigerant Capacity
P
A
1,3,5 kW 560.5 601.2 630.7
Rated Power Input D
A
kW 181.4 197.1 211.6
Rated EER
DC,A
3.09 3.05 2.98
Declared Refrigerant Capacity P
B
1,3,5 kW 528.1 / 426.3 565.3 / 461.5 599.2 / 486.3
Declared Power Input D
B
kW 123.1 / 96.6 131.8 / 105.1 143.5 / 112.5
Declared EER
DC,B
4.29 / 4.41 4.29 / 4.39 4.17 / 4.32
Declared Refrigerant Capacity P
C
1,3,5 kW 572.4 / 462.2 614.4 / 501.5 653.4 / 528.2
Declared Power Input D
C
kW 102.6 / 80.3 110.2 / 87.7 120.3 / 94.0
Declared EER
DC,C
5.58 / 5.75 5.57 / 5.72 5.43 / 5.62
Declared Refrigerant Capacity P
D
1,3,5 kW 445.5 / 356.6 477.4 / 381.8 500.8 / 411.2
Declared Power Input D
D
kW 45.5 / 54.1 48.3 / 57.4 51.1 / 62.2
Declared EER
DC,D
9.80 / 6.59 9.87 / 6.65 9.79 / 6.61
SSCEE
2,3,5 % 173.8 171.7 168.7
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 563.3 604.8 634.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 560.5 601.2 630.7
Declared EER
d
35°C
3.09 3.05 2.98
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 528.1 / 426.3 565.3 / 461.5 599.2 / 486.3
Declared EER
d
30°C
4.29 / 4.41 4.29 / 4.39 4.17 / 4.32
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 572.4 / 462.2 614.4 / 501.5 653.4 / 528.2
Declared EER
d
25°C
5.58 / 5.75 5.57 / 5.72 5.43 / 5.62
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 445.5 / 356.6 477.4 / 381.8 500.8 / 411.2
Declared EER
d
20°C
9.80 / 6.59 9.87 / 6.65 9.79 / 6.61
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 230259 230259 230259
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 3.372 4.244 4.344
Standby Mode P
SB
kW 0.311 0.311 0.311
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF061DX-16DVV0, DCF066DX-16FVW0, DCF069DX-16FWW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections