Notes: Units DCF062DX-12FVW0 DCF065DX-12FWW0 DCF069TX-13GPPY
SEPR
1,3,5 6.39 6.27 6.06
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 659540 702561 780523
Rated Refrigerant Capacity
P
A
1,3,5 kW 568.7 594.4 638.6
Rated Power Input D
A
kW 209.9 226.0 242.8
Rated EER
DC,A
2.71 2.63 2.63
Declared Refrigerant Capacity P
B
1,3,5 kW 547.2 / 452.8 577.6 / 476.3 646.8 / 553.3
Declared Power Input D
B
kW 138.2 / 109.5 151.8 / 117.5 172.4 / 147.1
Declared EER
DC,B
3.96 / 4.13 3.81 / 4.05 3.75 / 3.76
Declared Refrigerant Capacity P
C
1,3,5 kW 600.0 / 492.4 518.4 / 392.2 610.6 / 491.1
Declared Power Input D
C
kW 115.8 / 91.7 98.5 / 72.9 123.0 / 95.1
Declared EER
DC,C
5.18 / 5.37 5.26 / 5.38 4.96 / 5.16
Declared Refrigerant Capacity P
D
1,3,5 kW 451.4 / 382.0 471.6 / 411.1 507.0 / 386.4
Declared Power Input D
D
kW 47.0 / 57.8 49.5 / 63.2 55.0 / 59.1
Declared EER
DC,D
9.61 / 6.61 9.52 / 6.50 9.22 / 6.54
SSCEE
2,3,5 % 163.3 159.1 153.7
SSCEE Tier
6 Tier 1 (2018) Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 572.2 n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 568.7 n/a n/a
Declared EER
d
35°C
2.71 n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 547.2 / 452.8 n/a n/a
Declared EER
d
30°C
3.96 / 4.13 n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 600.0 / 492.4 n/a n/a
Declared EER
d
25°C
5.18 / 5.37 n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 451.4 / 382.0 n/a n/a
Declared EER
d
20°C
9.61 / 6.61 n/a n/a
Sound Power Level LWA
dB(A) n/a n/a
Air ow rate
m³/h 172694 n/a n/a
Off mode P
OFF
kW 0.157 n/a n/a
Thermostat-off mode P
TO
kW 4.096 n/a n/a
Standby Mode P
SB
kW 0.291 n/a n/a
Crankcase heater mode P
CK
kW 0.000 n/a n/a
Technical Data
Ecodesign
DCF062DX-12FVW0, DCF065DX-12FWW0, DCF069TX-13GPPY
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections