Notes: Units DCF055DR-12DPV0 DCF057DR-12DYY0 DCF059DR-13DYV0
SEPR
1,3,5 6.17 6.15 6.19
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 600592 626864 647362
Rated Refrigerant Capacity
P
A
1,3,5 kW 500.3 520.7 540.8
Rated Power Input D
A
kW 166.8 178.9 182.7
Rated EER
DC,A
3 2.91 2.96
Declared Refrigerant Capacity P
B
1,3,5 kW 558.5 / 456.9 487.4 / 394.1 602.7 / 501.8
Declared Power Input D
B
kW 137.4 / 109.8 121.1 / 94.4 150.8 / 123.2
Declared EER
DC,B
4.06 / 4.16 4.02 / 4.18 4.00 / 4.07
Declared Refrigerant Capacity P
C
1,3,5 kW 496.2 / 382.8 528.0 / 427.5 543.6 / 443.1
Declared Power Input D
C
kW 92.1 / 70.9 101.3 / 78.7 103.0 / 80.4
Declared EER
DC,C
5.39 / 5.40 5.21 / 5.43 5.28 / 5.51
Declared Refrigerant Capacity P
D
1,3,5 kW 396.6 / 260.5 413.9 / 334.7 429.8 / 341.9
Declared Power Input D
D
kW 46.7 / 40.4 48.1 / 51.3 50.3 / 52.4
Declared EER
DC,D
8.49 / 6.45 8.60 / 6.52 8.54 / 6.52
SSCEE
2,3,5 % 161.6 166.3 167.4
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 504.1 523.4 543.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 500.3 520.7 540.8
Declared EER
d
35°C
3 2.91 2.96
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 558.5 / 456.9 487.4 / 394.1 602.7 / 501.8
Declared EER
d
30°C
4.06 / 4.16 4.02 / 4.18 4.00 / 4.07
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 496.2 / 382.8 528.0 / 427.5 543.6 / 443.1
Declared EER
d
25°C
5.39 / 5.40 5.21 / 5.43 5.28 / 5.51
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 396.6 / 260.5 413.9 / 334.7 429.8 / 341.9
Declared EER
d
20°C
8.49 / 6.45 8.60 / 6.52 8.54 / 6.52
Sound Power Level LWA
dB(A) 91 91 91
Air ow rate
m³/h 253929 253929 275090
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 4.217 3.151 3.334
Standby Mode P
SB
kW 0.279 0.291 0.296
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF055DR-12DPV0, DCF057DR-12DYY0, DCF059DR-13DYV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)