Notes: Units DCF098TR-21HVVW DCF101TR-21HVWW DCF103TR-21HWWW
SEPR
1,3,5 6.23 6.17 6.10
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1054355 1101407 1146261
Rated Refrigerant Capacity
P
A
1,3,5 kW 886.6 917.8 943.6
Rated Power Input D
A
kW 297.5 312.2 325.4
Rated EER
DC,A
2.98 2.94 2.9
Declared Refrigerant Capacity P
B
1,3,5 kW 874.4 / 771.8 908.7 / 795.3 937.9 / 825.3
Declared Power Input D
B
kW 212.1 / 184.4 224.7 / 192.3 235.6 / 203.3
Declared EER
DC,B
4.12 / 4.19 4.04 / 4.14 3.98 / 4.06
Declared Refrigerant Capacity P
C
1,3,5 kW 835.7 / 725.0 860.7 / 750.0 892.4 / 771.0
Declared Power Input D
C
kW 154.0 / 130.8 160.6 / 137.4 169.7 / 142.5
Declared EER
DC,C
5.43 / 5.54 5.36 / 5.46 5.26 / 5.41
Declared Refrigerant Capacity P
D
1,3,5 kW 703.9 / 619.0 728.4 / 646.3 749.7 / 670.2
Declared Power Input D
D
kW 82.6 / 93.8 85.4 / 98.9 88.8 / 102.6
Declared EER
DC,D
8.53 / 6.60 8.53 / 6.54 8.45 / 6.53
SSCEE
2,3,5 % 166.1 163.4 163.8
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 892.1 923.7 948.9
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 886.6 917.8 943.6
Declared EER
d
35°C
2.98 2.94 2.9
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 874.4 / 771.8 908.7 / 795.3 937.9 / 825.3
Declared EER
d
30°C
4.12 / 4.19 4.04 / 4.14 3.98 / 4.06
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 835.7 / 725.0 860.7 / 750.0 892.4 / 771.0
Declared EER
d
25°C
5.43 / 5.54 5.36 / 5.46 5.26 / 5.41
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 703.9 / 619.0 728.4 / 646.3 749.7 / 670.2
Declared EER
d
20°C
8.53 / 6.60 8.53 / 6.54 8.45 / 6.53
Sound Power Level LWA
dB(A) 94 95 95
Air ow rate
m³/h 444376 444376 444376
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 6.380 6.946 6.239
Standby Mode P
SB
kW 0.383 0.383 0.383
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF098TR-21HVVW, DCF101TR-21HVWW, DCF103TR-21HWWW
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections