Technical Data
Ecodesign
DCC080TR-16GYYV, DCC082TR-17GYVV, DCC085TR-18GVVV
Notes: Units DCC080TR-16GYYV DCC082TR-17GYVV DCC085TR-18GVVV
SEPR
1,3,5 5.50 5.54 5.59
SEPR Tier
Tier 1 (2018) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1062924 1080748 1095752
Rated Refrigerant Capacity
P
A
1,3,5 kW 788.4 807.8 827.1
Rated Power Input D
A
kW 272.8 276.6 280.4
Rated EER
DC,A
2.89 2.92 2.95
Declared Refrigerant Capacity P
B
1,3,5 kW 776.1 / 685.2 797.8 / 699.3 819.5 / 721.0
Declared Power Input D
B
kW 197.2 / 170.0 199.6 / 171.8 202.0 / 174.2
Declared EER
DC,B
3.94 / 4.03 4.00 / 4.07 4.06 / 4.14
Declared Refrigerant Capacity P
C
1,3,5 kW 738.9 / 641.3 754.0 / 656.4 777.2 / 671.4
Declared Power Input D
C
kW 142.0 / 119.0 143.4 / 120.4 145.1 / 121.8
Declared EER
DC,C
5.20 / 5.39 5.26 / 5.45 5.36 / 5.51
Declared Refrigerant Capacity P
D
1,3,5 kW 671.6 / 554.6 685.0 / 568.1 698.5 / 581.5
Declared Power Input D
D
kW 102.1 / 84.8 103.9 / 86.7 105.7 / 88.5
Declared EER
DC,D
6.58 / 6.54 6.59 / 6.56 6.61 / 6.57
SSCEE
2,3,5 % 168.3 169.2 171.0
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 791.2 810.7 830.3
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 788.4 807.8 827.1
Declared EER
d
35°C
2.89 2.92 2.95
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 776.1 / 685.2 797.8 / 699.3 819.5 / 721.0
Declared EER
d
30°C
3.94 / 4.03 4.00 / 4.07 4.06 / 4.14
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 738.9 / 641.3 754.0 / 656.4 777.2 / 671.4
Declared EER
d
25°C
5.20 / 5.39 5.26 / 5.45 5.36 / 5.51
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 671.6 / 554.6 685.0 / 568.1 698.5 / 581.5
Declared EER
d
20°C
6.58 / 6.54 6.59 / 6.56 6.61 / 6.57
Sound Power Level LWA
dB(A) 94 94 94
Air ow rate
m³/h 371190 394390 417589
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.393 3.620 3.835
Standby Mode P
SB
kW 0.358 0.363 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)