Technical Data
Ecodesign
DCC015DX-04ADF0, DCC016DX-04AJJ0, DCC018DX-04BJK0
Notes: Units DCC090TR-21GVVW DCC093TR-21GVWW DCC096TR-21GWWW
SEPR
1,3,5 5.77 5.71 5.64
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1125163 1177854 1233281
Rated Refrigerant Capacity
P
A
1,3,5 kW 876.9 908 939.1
Rated Power Input D
A
kW 286.6 300.7 315.1
Rated EER
DC,A
3.06 3.02 2.98
Declared Refrigerant Capacity P
B
1,3,5 kW 862.3 / 761.1 896.4 / 784.5 930.5 / 818.6
Declared Power Input D
B
kW 203.8 / 177.0 215.7 / 184.4 227.6 / 196.3
Declared EER
DC,B
4.23 / 4.30 4.16 / 4.26 4.09 / 4.17
Declared Refrigerant Capacity P
C
1,3,5 kW 822.1 / 713.3 846.8 / 738.0 882.7 / 762.6
Declared Power Input D
C
kW 147.3 / 124.8 153.5 / 131.0 163.5 / 137.1
Declared EER
DC,C
5.58 / 5.72 5.52 / 5.64 5.40 / 5.56
Declared Refrigerant Capacity P
D
1,3,5 kW 739.0 / 606.4 765.9 / 633.2 792.7 / 660.0
Declared Power Input D
D
kW 109.5 / 90.0 114.2 / 94.8 118.9 / 99.5
Declared EER
DC,D
6.75 / 6.73 6.71 / 6.68 6.66 / 6.63
SSCEE
2,3,5 % 178.9 176.5 173.6
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 879.5 910.8 942.1
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 876.9 908 939.1
Declared EER
d
35°C
3.06 3.02 2.98
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 862.3 / 761.1 896.4 / 784.5 930.5 / 818.6
Declared EER
d
30°C
4.23 / 4.30 4.16 / 4.26 4.09 / 4.17
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 822.1 / 713.3 846.8 / 738.0 882.7 / 762.6
Declared EER
d
25°C
5.58 / 5.72 5.52 / 5.64 5.40 / 5.56
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 739.0 / 606.4 765.9 / 633.2 792.7 / 660.0
Declared EER
d
20°C
6.75 / 6.73 6.71 / 6.68 6.66 / 6.63
Sound Power Level LWA
dB(A) 94 94 95
Air ow rate
m³/h 487187 487187 487187
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.313 3.607 3.916
Standby Mode P
SB
kW 0.383 0.383 0.383
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections