Notes: Units DCF047DX-09DXY0 DCF049DX-09DPY0 DCF051DX-10DPV0
SEPR
1,3,5 6.33 6.08 6.15
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 506689 542581 565609
Rated Refrigerant Capacity
P
A
1,3,5 kW 433 445.6 469.7
Rated Power Input D
A
kW 163.4 169.4 172.7
Rated EER
DC,A
2.65 2.63 2.72
Declared Refrigerant Capacity P
B
1,3,5 kW 411.1 / 346.3 426.8 / 331.5 442.0 / 338.6
Declared Power Input D
B
kW 106.7 / 85.5 111.5 / 86.1 113.6 / 87.4
Declared EER
DC,B
3.85 / 4.05 3.83 / 3.85 3.89 / 3.88
Declared Refrigerant Capacity P
C
1,3,5 kW 376.7 / 274.4 469.1 / 365.6 485.0 / 373.3
Declared Power Input D
C
kW 71.6 / 50.3 93.6 / 72.2 95.1 / 73.2
Declared EER
DC,C
5.26 / 5.45 5.01 / 5.06 5.10 / 5.10
Declared Refrigerant Capacity P
D
1,3,5 kW 343.7 / 287.8 353.2 / 253.6 372.3 / 260.8
Declared Power Input D
D
kW 35.2 / 43.6 38.3 / 39.0 40.0 / 40.3
Declared EER
DC,D
9.76 / 6.61 9.23 / 6.50 9.31 / 6.48
SSCEE
2,3,5 % 161.0 152.3 153.3
SSCEE Tier
6 Tier 1 (2018) Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 435.7 448.8 n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 433 445.6 n/a
Declared EER
d
35°C
2.65 2.63 n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 411.1 / 346.3 426.8 / 331.5 n/a
Declared EER
d
30°C
3.85 / 4.05 3.83 / 3.85 n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 376.7 / 274.4 469.1 / 365.6 n/a
Declared EER
d
25°C
5.26 / 5.45 5.01 / 5.06 n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 343.7 / 287.8 353.2 / 253.6 n/a
Declared EER
d
20°C
9.76 / 6.61 9.23 / 6.50 n/a
Sound Power Level LWA
dB(A) n/a
Air ow rate
m³/h 129520 129520 n/a
Off mode P
OFF
kW 0.157 0.157 n/a
Thermostat-off mode P
TO
kW 3.025 3.595 n/a
Standby Mode P
SB
kW 0.276 0.264 n/a
Crankcase heater mode P
CK
kW 0.000 0.000 n/a
Technical Data
Ecodesign
DCF047DX-09DXY0, DCF049DX-09DPY0, DCF051DX-10DPV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections