Notes: Units DCF068DX-14FWW0 DCF073TX-16GPPY DCF078TX-17GPYY
SEPR
1,3,5 6.47 6.54 6.48
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 704999 756106 820674
Rated Refrigerant Capacity
P
A
1,3,5 kW 615.2 667.5 717.3
Rated Power Input D
A
kW 217.4 231.8 250.8
Rated EER
DC,A
2.83 2.88 2.86
Declared Refrigerant Capacity P
B
1,3,5 kW 590.3 / 482.6 667.3 / 572.2 723.1 / 634.0
Declared Power Input D
B
kW 146.9 / 114.8 164.8 / 140.5 180.7 / 154.2
Declared EER
DC,B
4.02 / 4.20 4.05 / 4.07 4.00 / 4.11
Declared Refrigerant Capacity P
C
1,3,5 kW 645.4 / 523.4 627.7 / 501.7 691.8 / 587.1
Declared Power Input D
C
kW 123.0 / 95.8 118.0 / 91.7 129.3 / 108.9
Declared EER
DC,C
5.25 / 5.46 5.32 / 5.47 5.35 / 5.39
Declared Refrigerant Capacity P
D
1,3,5 kW 488.4 / 411.2 530.2 / 525.8 569.2 / 504.8
Declared Power Input D
D
kW 50.5 / 62.5 52.5 / 80.4 58.0 / 78.2
Declared EER
DC,D
9.68 / 6.58 10.10 / 6.54 9.82 / 6.46
SSCEE
2,3,5 % 164.9 162.5 162.4
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 619.1 671.3 722
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 615.2 667.5 717.3
Declared EER
d
35°C
2.83 2.88 2.86
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 590.3 / 482.6 667.3 / 572.2 723.1 / 634.0
Declared EER
d
30°C
4.02 / 4.20 4.05 / 4.07 4.00 / 4.11
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 645.4 / 523.4 627.7 / 501.7 691.8 / 587.1
Declared EER
d
25°C
5.25 / 5.46 5.32 / 5.47 5.35 / 5.39
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 488.4 / 411.2 530.2 / 525.8 569.2 / 504.8
Declared EER
d
20°C
9.68 / 6.58 10.10 / 6.54 9.82 / 6.46
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 201476 230259 244650
Off mode P
OFF
kW 0.157 0.169 0.169
Thermostat-off mode P
TO
kW 4.295 4.374 5.300
Standby Mode P
SB
kW 0.301 0.335 0.351
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF047DX-09DXY0, DCF049DX-09DPY0, DCF051DX-10DPV0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)