Notes: Units DCF075TR-16GPPY DCF080TR-17GPYY DCF085TR-18GYYY
SEPR
1,3,5 6.13 6.12 6.02
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 828430 894134 961577
Rated Refrigerant Capacity
P
A
1,3,5 kW 685.9 738.3 781.2
Rated Power Input D
A
kW 232.5 252.0 270.3
Rated EER
DC,A
2.95 2.93 2.89
Declared Refrigerant Capacity P
B
1,3,5 kW 673.7 / 578.5 730.7 / 637.3 777.8 / 684.4
Declared Power Input D
B
kW 165.7 / 141.3 181.7 / 154.9 196.8 / 170.0
Declared EER
DC,B
4.07 / 4.09 4.02 / 4.11 3.95 / 4.03
Declared Refrigerant Capacity P
C
1,3,5 kW 628.0 / 501.8 691.9 / 587.2 741.9 / 641.0
Declared Power Input D
C
kW 118.3 / 92.0 129.7 / 109.3 142.4 / 119.8
Declared EER
DC,C
5.31 / 5.45 5.33 / 5.37 5.21 / 5.35
Declared Refrigerant Capacity P
D
1,3,5 kW 544.6 / 525.6 585.7 / 504.5 619.4 / 558.0
Declared Power Input D
D
kW 64.0 / 80.6 69.2 / 78.5 74.9 / 86.9
Declared EER
DC,D
8.52 / 6.52 8.46 / 6.42 8.27 / 6.42
SSCEE
2,3,5 % 162.3 162.5 159.1
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 690 743.3 n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 685.9 738.3 n/a
Declared EER
d
35°C
2.95 2.93 n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 673.7 / 578.5 730.7 / 637.3 n/a
Declared EER
d
30°C
4.07 / 4.09 4.02 / 4.11 n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 628.0 / 501.8 691.9 / 587.2 n/a
Declared EER
d
25°C
5.31 / 5.45 5.33 / 5.37 n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 544.6 / 525.6 585.7 / 504.5 n/a
Declared EER
d
20°C
8.52 / 6.52 8.46 / 6.42 n/a
Sound Power Level LWA
dB(A) 93 93 n/a
Air ow rate
m³/h 338572 359733 n/a
Off mode P
OFF
kW 0.169 0.169 n/a
Thermostat-off mode P
TO
kW 4.670 5.688 n/a
Standby Mode P
SB
kW 0.335 0.351 n/a
Crankcase heater mode P
CK
kW 0.000 0.000 n/a
Technical Data
Ecodesign
DCF075TR-16GPPY, DCF080TR-17GPYY, DCF085TR-18GYYY
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections