Technical Data
Ecodesign
DCC082TR-19GYYV, DCC084TR-20GYVV, DCC087TR-21GVVV
Notes: Units DCC082TR-19GYYV DCC084TR-20GYVV DCC087TR-21GVVV
SEPR
1,3,5 5.64 5.67 5.71
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1047911 1067783 1085652
Rated Refrigerant Capacity
P
A
1,3,5 kW 798.2 817.6 836.9
Rated Power Input D
A
kW 264.3 268.9 272.6
Rated EER
DC,A
3.02 3.04 3.07
Declared Refrigerant Capacity P
B
1,3,5 kW 785.6 / 692.9 806.8 / 706.7 827.9 / 727.8
Declared Power Input D
B
kW 191.1 / 165.2 193.9 / 167.2 196.8 / 170.1
Declared EER
DC,B
4.11 / 4.20 4.16 / 4.23 4.21 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW 747.4 / 647.8 762.0 / 662.4 784.5 / 677.0
Declared Power Input D
C
kW 137.7 / 115.8 139.3 / 117.4 141.5 / 119.1
Declared EER
DC,C
5.43 / 5.59 5.47 / 5.64 5.54 / 5.69
Declared Refrigerant Capacity P
D
1,3,5 kW 671.5 / 554.5 685.0 / 568.0 698.5 / 581.5
Declared Power Input D
D
kW 101.3 / 84.3 103.3 / 86.2 105.3 / 88.2
Declared EER
DC,D
6.63 / 6.58 6.63 / 6.59 6.63 / 6.59
SSCEE
2,3,5 % 172.9 173.5 174.7
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 801.1 820.7 840.2
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 798.2 817.6 836.9
Declared EER
d
35°C
3.02 3.04 3.07
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 785.6 / 692.9 806.8 / 706.7 827.9 / 727.8
Declared EER
d
30°C
4.11 / 4.20 4.16 / 4.23 4.21 / 4.28
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 747.4 / 647.8 762.0 / 662.4 784.5 / 677.0
Declared EER
d
25°C
5.43 / 5.59 5.47 / 5.64 5.54 / 5.69
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 671.5 / 554.5 685.0 / 568.0 698.5 / 581.5
Declared EER
d
20°C
6.63 / 6.58 6.63 / 6.59 6.63 / 6.59
Sound Power Level LWA
dB(A) 93 93 93
Air ow rate
m³/h 440788 463988 487187
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.546 3.758 4.010
Standby Mode P
SB
kW 0.373 0.378 0.383
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections