Notes: Units DCF100TR-18HWWW DCF051DR-11DXY0 DCF053DR-11DPY0
SEPR
1,3,5 5.88 6.26 6.16
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1173022 548291 577476
Rated Refrigerant Capacity
P
A
1,3,5 kW 931.7 463.3 480.2
Rated Power Input D
A
kW 335.1 157.1 162.8
Rated EER
DC,A
2.78 2.95 2.95
Declared Refrigerant Capacity P
B
1,3,5 kW 926.4 / 815.9 517.3 / 424.3 536.3 / 442.4
Declared Power Input D
B
kW 242.9 / 209.2 129.9 / 103.2 134.5 / 107.7
Declared EER
DC,B
3.81 / 3.90 3.98 / 4.11 3.99 / 4.11
Declared Refrigerant Capacity P
C
1,3,5 kW 882.6 / 763.3 461.1 / 381.7 480.5 / 375.2
Declared Power Input D
C
kW 174.9 / 146.5 86.4 / 69.4 90.3 / 69.8
Declared EER
DC,C
5.05 / 5.21 5.34 / 5.50 5.32 / 5.37
Declared Refrigerant Capacity P
D
1,3,5 kW 739.9 / 670.0 367.8 / 287.5 380.7 / 253.2
Declared Power Input D
D
kW 90.2 / 103.9 42.0 / 43.3 44.4 / 39.2
Declared EER
DC,D
8.20 / 6.45 8.76 / 6.65 8.57 / 6.46
SSCEE
2,3,5 % 158.5 166.7 161.1
SSCEE Tier
6 Not Compliant Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 n/a 466.2 483.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a 463.3 480.2
Declared EER
d
35°C
n/a 2.95 2.95
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a 517.3 / 424.3 536.3 / 442.4
Declared EER
d
30°C
n/a 3.98 / 4.11 3.99 / 4.11
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a 461.1 / 381.7 480.5 / 375.2
Declared EER
d
25°C
n/a 5.34 / 5.50 5.32 / 5.37
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a 367.8 / 287.5 380.7 / 253.2
Declared EER
d
20°C
n/a 8.76 / 6.65 8.57 / 6.46
Sound Power Level LWA
dB(A) n/a 90 91
Air ow rate
m³/h n/a 232768 232768
Off mode P
OFF
kW n/a 0.157 0.157
Thermostat-off mode P
TO
kW n/a 3.216 3.940
Standby Mode P
SB
kW n/a 0.286 0.274
Crankcase heater mode P
CK
kW n/a 0.000 0.000
Technical Data
Ecodesign
DCF100TR-18HWWW, DCF051DR-11DXY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections