Technical Data
Ecodesign
DCF074TR-11GPYY, DCF079TR-12GYYY, DCF082TR-13HYYV
Notes: Units DCF074TR-11GPYY DCF079TR-12GYYY DCF082TR-13HYYV
SEPR
1,3,5 5.41 5.43 5.52
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 950303 1008635 1027785
Rated Refrigerant Capacity
P
A
1,3,5 kW 693.4 739.4 765.2
Rated Power Input D
A
kW 271.9 290.0 293.2
Rated EER
DC,A
2.55 2.55 2.61
Declared Refrigerant Capacity P
B
1,3,5 kW 700.4 / 612.2 750.6 / 662.4 765.7 / 677.5
Declared Power Input D
B
kW 198.2 / 168.3 213.1 / 183.3 213.8 / 183.9
Declared EER
DC,B
3.53 / 3.64 3.52 / 3.61 3.58 / 3.68
Declared Refrigerant Capacity P
C
1,3,5 kW 667.1 / 566.4 718.6 / 622.8 733.4 / 637.7
Declared Power Input D
C
kW 142.1 / 119.5 154.4 / 128.9 154.6 / 129.1
Declared EER
DC,C
4.70 / 4.74 4.65 / 4.83 4.75 / 4.94
Declared Refrigerant Capacity P
D
1,3,5 kW 549.4 / 490.0 585.6 / 553.2 606.9 / 557.8
Declared Power Input D
D
kW 73.4 / 84.6 78.4 / 91.5 80.3 / 91.7
Declared EER
DC,D
7.49 / 5.79 7.47 / 6.05 7.56 / 6.08
SSCEE
2,3,5 % 145.9 146.3 149.7
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections