Technical Data DCF
Ecodesign
DCF046DR-07DXY0, DCF048DR-07DPY0, DCF051DR-08DPV0
Notes: Units DCF046DR-07DXY0 DCF048DR-07DPY0 DCF051DR-08DPV0
SEPR 1,3,5 5.61 5.44 5.51
SEPR Tier Tier 2 (2021) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption kWh/a 575048 610947 636756
Rated Refrigerant Capacity
P
A
1,3,5 kW 435.3 448.9 474
Rated Power Input D
A
kW 170.7 176.0 180.2
Rated EER
DC,A
2.55 2.55 2.63
Declared Refrigerant Capacity P
B
1,3,5 kW 407.1 / 339.6 422.7 / 329.1 535.9 / 438.2
Declared Power Input D
B
kW 112.7 / 89.9 117.7 / 90.8 149.5 / 119.2
Declared EER
DC,B
3.61 / 3.78 3.59 / 3.62 3.58 / 3.68
Declared Refrigerant Capacity P
C
1,3,5 kW 443.2 / 369.1 461.6 / 360.4 478.5 / 368.4
Declared Power Input D
C
kW 95.2 / 75.6 99.7 / 77.1 100.8 / 77.9
Declared EER
DC,C
4.65 / 4.89 4.63 / 4.67 4.75 / 4.73
Declared Refrigerant Capacity P
D
1,3,5 kW 345.1 / 284.4 355.4 / 253.1 375.2 / 260.4
Declared Power Input D
D
kW 43.2 / 45.8 45.9 / 40.3 48.3 / 41.4
Declared EER
DC,D
7.99 / 6.20 7.74 / 6.29 7.77 / 6.29
SSCEE 2,3,5 % 150.4 142.5 144.2
SSCEE Tier 6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc 2,3,5 kW n/a n/a n/a
Declared EER
d
35°C n/a n/a n/a
Declared Cooling Capacity 30°C Pdc 2,3,5 kW n/a n/a n/a
Declared EER
d
30°C n/a n/a n/a
Declared Cooling Capacity 25°C Pdc 2,3,5 kW n/a n/a n/a
Declared EER
d
25°C n/a n/a n/a
Declared Cooling Capacity 20°C Pdc 2,3,5 kW n/a n/a n/a
Declared EER
d
20°C n/a n/a n/a
Sound Power Level LWA dB(A) n/a n/a n/a
Air ow rate m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
267
Chiller Technical Manual 7267818 V1.13.0_01_2018