Technical Data
Ecodesign
DCC048DX-10EPV0, DCC049DX-10EYY0, DCC053DX-11DYV0
Notes: Units DCC048DX-10EPV0 DCC049DX-10EYY0 DCC053DX-11DYV0
SEPR
1,3,5 5.36 5.34 5.57
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 640487 669740 685192
Rated Refrigerant Capacity
P
A
1,3,5 kW 463.1 482.8 515.3
Rated Power Input D
A
kW 165.4 179.5 182.7
Rated EER
DC,A
2.8 2.69 2.82
Declared Refrigerant Capacity P
B
1,3,5 kW 523.1 / 430.4 461.6 / 378.2 487.5 / 402.8
Declared Power Input D
B
kW 135.6 / 108.2 120.7 / 93.6 122.6 / 95.3
Declared EER
DC,B
3.86 / 3.98 3.82 / 4.04 3.98 / 4.23
Declared Refrigerant Capacity P
C
1,3,5 kW 467.9 / 361.4 500.6 / 406.4 530.2 / 434.1
Declared Power Input D
C
kW 90.2 / 69.1 100.7 / 77.9 102.3 / 79.3
Declared EER
DC,C
5.19 / 5.23 4.97 / 5.22 5.18 / 5.47
Declared Refrigerant Capacity P
D
1,3,5 kW 380.3 / 247.9 424.9 / 318.2 453.4 / 336.3
Declared Power Input D
D
kW 60.7 / 38.0 66.5 / 50.2 68.2 / 50.9
Declared EER
DC,D
6.27 / 6.53 6.39 / 6.34 6.65 / 6.60
SSCEE
2,3,5 % 162.9 163.9 172.2
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 464.8 484.7 516.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 463.1 482.8 515.3
Declared EER
d
35°C
2.8 2.69 2.82
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 523.1 / 430.4 461.6 / 378.2 487.5 / 402.8
Declared EER
d
30°C
3.86 / 3.98 3.82 / 4.04 3.98 / 4.23
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 467.9 / 361.4 500.6 / 406.4 530.2 / 434.1
Declared EER
d
25°C
5.19 / 5.23 4.97 / 5.22 5.18 / 5.47
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 380.3 / 247.9 424.9 / 318.2 453.4 / 336.3
Declared EER
d
20°C
6.27 / 6.53 6.39 / 6.34 6.65 / 6.60
Sound Power Level LWA
dB(A) 88 86 87
Air ow rate
m³/h 158929 158929 174822
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.061 2.279 1.768
Standby Mode P
SB
kW 0.269 0.281 0.286
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections