Technical Data
Ecodesign
DCC080TX-19GYYV, DCC082TX-20GYVV, DCC085TX-21GVVV
Notes: Units DCC080TX-19GYYV DCC082TX-20GYVV DCC085TX-21GVVV
SEPR
1,3,5 5.66 5.69 5.72
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1023586 1045105 1064742
Rated Refrigerant Capacity
P
A
1,3,5 kW 781.6 802.1 822.6
Rated Power Input D
A
kW 263.2 267.4 271.5
Rated EER
DC,A
2.97 3 3.03
Declared Refrigerant Capacity P
B
1,3,5 kW 779.8 / 689.9 802.3 / 703.6 824.7 / 726.0
Declared Power Input D
B
kW 190.4 / 164.7 193.2 / 166.8 196.1 / 169.6
Declared EER
DC,B
4.10 / 4.19 4.15 / 4.22 4.20 / 4.28
Declared Refrigerant Capacity P
C
1,3,5 kW 747.5 / 647.9 762.2 / 662.5 784.6 / 677.2
Declared Power Input D
C
kW 137.6 / 115.7 139.2 / 117.3 141.4 / 119.0
Declared EER
DC,C
5.43 / 5.60 5.48 / 5.65 5.55 / 5.69
Declared Refrigerant Capacity P
D
1,3,5 kW 671.7 / 554.7 685.1 / 568.2 698.6 / 581.6
Declared Power Input D
D
kW 101.2 / 84.1 103.2 / 86.1 105.2 / 88.1
Declared EER
DC,D
6.64 / 6.59 6.64 / 6.60 6.64 / 6.60
SSCEE
2,3,5 % 173.3 173.9 175.1
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 784.3 805 825.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 781.6 802.1 822.6
Declared EER
d
35°C
2.97 3 3.03
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 779.8 / 689.9 802.3 / 703.6 824.7 / 726.0
Declared EER
d
30°C
4.10 / 4.19 4.15 / 4.22 4.20 / 4.28
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 747.5 / 647.9 762.2 / 662.5 784.6 / 677.2
Declared EER
d
25°C
5.43 / 5.60 5.48 / 5.65 5.55 / 5.69
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 671.7 / 554.7 685.1 / 568.2 698.6 / 581.6
Declared EER
d
20°C
6.64 / 6.59 6.64 / 6.60 6.64 / 6.60
Sound Power Level LWA
dB(A) 89 89 90
Air ow rate
m³/h 301965 317858 333751
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.369 3.588 3.845
Standby Mode P
SB
kW 0.373 0.378 0.383
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections