Notes: Units DCF084TX-21GYYY DCF087TX-22HYYV
SEPR
1,3,5 6.61 6.69
SEPR Tier
Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 873802 886849
Rated Refrigerant Capacity
P
A
1,3,5 kW 779.6 800.7
Rated Power Input D
A
kW 260.7 264.3
Rated EER
DC,A
2.99 3.03
Declared Refrigerant Capacity P
B
1,3,5 kW 783.6 / 690.1 796.9 / 703.4
Declared Power Input D
B
kW 190.9 / 165.4 192.2 / 166.7
Declared EER
DC,B
4.10 / 4.17 4.15 / 4.22
Declared Refrigerant Capacity P
C
1,3,5 kW 749.6 / 647.1 762.0 / 659.8
Declared Power Input D
C
kW 138.4 / 116.8 139.2 / 117.6
Declared EER
DC,C
5.41 / 5.54 5.47 / 5.61
Declared Refrigerant Capacity P
D
1,3,5 kW 618.3 / 558.3 635.9 / 562.5
Declared Power Input D
D
kW 61.9 / 86.1 62.8 / 86.4
Declared EER
DC,D
9.98 / 6.48 10.13 / 6.51
SSCEE
2,3,5 % 163.8 167.3
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 784.9 805.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 779.6 800.7
Declared EER
d
35°C
2.99 3.03
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 783.6 / 690.1 796.9 / 703.4
Declared EER
d
30°C
4.10 / 4.17 4.15 / 4.22
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 749.6 / 647.1 762.0 / 659.8
Declared EER
d
25°C
5.41 / 5.54 5.47 / 5.61
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 618.3 / 558.3 635.9 / 562.5
Declared EER
d
20°C
9.98 / 6.48 10.13 / 6.51
Sound Power Level LWA
dB(A)
Air ow rate
m³/h 302214 316606
Off mode P
OFF
kW 0.169 0.169
Thermostat-off mode P
TO
kW 6.129 5.466
Standby Mode P
SB
kW 0.383 0.388
Crankcase heater mode P
CK
kW 0.000 0.000
Technical Data
Ecodesign
DCF084TX-21GYYY, DCF087TX-22HYYV
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections