Technical Data
Ecodesign
DCC056DR-10DVV0, DCC058DR-10DVW0, DCC061DR-10DWW0
Notes: Units DCC056DR-10DVV0 DCC058DR-10DVW0 DCC061DR-10DWW0
SEPR
1,3,5 5.49 5.40 5.28
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 744091 790592 854525
Rated Refrigerant Capacity
P
A
1,3,5 kW 551.7 576 608.7
Rated Power Input D
A
kW 194.3 207.9 223.8
Rated EER
DC,A
2.84 2.77 2.72
Declared Refrigerant Capacity P
B
1,3,5 kW 515.9 / 417.8 643.8 / 535.8 575.5 / 466.2
Declared Power Input D
B
kW 130.4 / 101.1 172.1 / 137.7 152.1 / 117.6
Declared EER
DC,B
3.96 / 4.13 3.74 / 3.89 3.78 / 3.96
Declared Refrigerant Capacity P
C
1,3,5 kW 556.6 / 451.2 577.3 / 472.5 620.2 / 503.3
Declared Power Input D
C
kW 109.2 / 84.4 115.1 / 90.4 127.7 / 98.4
Declared EER
DC,C
5.10 / 5.35 5.01 / 5.23 4.86 / 5.11
Declared Refrigerant Capacity P
D
1,3,5 kW 475.9 / 356.3 499.1 / 367.5 533.9 / 400.0
Declared Power Input D
D
kW 71.9 / 54.1 76.8 / 55.9 83.8 / 62.7
Declared EER
DC,D
6.62 / 6.59 6.50 / 6.57 6.37 / 6.38
SSCEE
2,3,5 % 167.3 166.8 159.7
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 553.9 578 n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 551.7 576 n/a
Declared EER
d
35°C
2.84 2.77 n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 515.9 / 417.8 643.8 / 535.8 n/a
Declared EER
d
30°C
3.96 / 4.13 3.74 / 3.89 n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 556.6 / 451.2 577.3 / 472.5 n/a
Declared EER
d
25°C
5.10 / 5.35 5.01 / 5.23 n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.9 / 356.3 499.1 / 367.5 n/a
Declared EER
d
20°C
6.62 / 6.59 6.50 / 6.57 n/a
Sound Power Level LWA
dB(A) 93 93 n/a
Air ow rate
m³/h 231994 231994 n/a
Off mode P
OFF
kW 0.157 0.157 n/a
Thermostat-off mode P
TO
kW 2.728 2.483 n/a
Standby Mode P
SB
kW 0.281 0.281 n/a
Crankcase heater mode P
CK
kW 0.000 0.000 n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections