Introduction
DeltaChill™ Air Cooled and FreeCool
14
Chiller Technical Manual 7267818 V1.13.0_01_2018
Construction
The base is fabricated from galvanised steel to ensure a rigid, durable, weatherproof construction.
The superstructure is manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide a
durable and weatherproof nish. Standard unit colour is Light Grey (RAL 7035).
Compressors and evaporator are mounted on a rigid galvanised heavy-duty sub frame.
Fully weatherproofed electrical panels are situated at one end of the unit.
Refrigeration
Compressor
Scroll compressors comprising:
Internal motor protection
Internal pressure relief
Non return valve
External discharge temperature protection
Oil sight glass
Each Tandem / Trio set has an oil equalisation line.
The compressors are mounted to the rigid galvanised heavy duty sub-frame with the use of vibration reducing isolation.
Compressor Staging
The sequence of the compressor staging has been engineered to optimise the units ESEER performance.
Refrigeration Pipework Components
Sight Glass
A liquid line sight glass is tted to give an indication of the state of the refrigerant within the system. If the sight glass
becomes yellow it’s an indication that the lter drier requires changing.
Liquid Line Ball Valves
Liquid line ball valves are tted to ensure ease of maintenance during shut down periods.
Discharge Line Ball Valves
Discharge line ball valves are tted to ensure ease of maintenance during shut down periods.
Filter Driers
Filter driers are tted to ensure that the expansion device is protected from any potential contaminants in the system.
This can be serviced with changeable inner cores.
HP / LP Transducers and Switches
HP / LP Transducers and switches are tted to the unit to protect against high or low pressures.
High pressure switches are manual reset.