Technical Data
Ecodesign
DCC077TR-13GYYV, DCC080TR-14GYVV, DCC083TR-15GVVV
Notes: Units DCC077TR-13GYYV DCC080TR-14GYVV DCC083TR-15GVVV
SEPR
1,3,5 5.27 5.34 5.43
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 1079383 1097288 1111590
Rated Refrigerant Capacity
P
A
1,3,5 kW 767 790.7 814.3
Rated Power Input D
A
kW 282.0 286.5 289.8
Rated EER
DC,A
2.72 2.76 2.81
Declared Refrigerant Capacity P
B
1,3,5 kW 763.7 / 675.0 786.2 / 689.6 808.6 / 712.0
Declared Power Input D
B
kW 205.6 / 176.6 207.3 / 178.1 209.0 / 179.9
Declared EER
DC,B
3.71 / 3.82 3.79 / 3.87 3.87 / 3.96
Declared Refrigerant Capacity P
C
1,3,5 kW 727.4 / 632.7 743.1 / 648.4 767.7 / 664.0
Declared Power Input D
C
kW 147.9 / 123.3 149.0 / 124.4 150.1 / 125.5
Declared EER
DC,C
4.92 / 5.13 4.99 / 5.21 5.11 / 5.29
Declared Refrigerant Capacity P
D
1,3,5 kW 669.4 / 552.4 684.0 / 567.1 698.7 / 581.7
Declared Power Input D
D
kW 104.9 / 87.2 105.9 / 88.2 106.9 / 89.2
Declared EER
DC,D
6.38 / 6.33 6.46 / 6.43 6.53 / 6.52
SSCEE
2,3,5 % 162.4 163.6 165.9
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 769.6 793.5 817.3
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 767 790.7 814.3
Declared EER
d
35°C
2.72 2.76 2.81
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 763.7 / 675.0 786.2 / 689.6 808.6 / 712.0
Declared EER
d
30°C
3.71 / 3.82 3.79 / 3.87 3.87 / 3.96
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 727.4 / 632.7 743.1 / 648.4 767.7 / 664.0
Declared EER
d
25°C
4.92 / 5.13 4.99 / 5.21 5.11 / 5.29
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 669.4 / 552.4 684.0 / 567.1 698.7 / 581.7
Declared EER
d
20°C
6.38 / 6.33 6.46 / 6.43 6.53 / 6.52
Sound Power Level LWA
dB(A) 94 94 95
Air ow rate
m³/h 301592 324791 347991
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.144 3.383 3.669
Standby Mode P
SB
kW 0.343 0.348 0.353
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)