Technical Data
Ecodesign
DCC059DX-16DVV0, DCC061DX-16DVW0, DCC065DX-16DWW0
Notes: Units DCC059DX-16DVV0 DCC061DX-16DVW0 DCC065DX-16DWW0
SEPR
1,3,5 5.89 5.81 5.72
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 715158 757802 815397
Rated Refrigerant Capacity
P
A
1,3,5 kW 568.1 594.1 629.1
Rated Power Input D
A
kW 178.1 191.0 206.3
Rated EER
DC,A
3.19 3.11 3.05
Declared Refrigerant Capacity P
B
1,3,5 kW 532.4 / 429.1 664.8 / 553.0 592.7 / 479.4
Declared Power Input D
B
kW 120.5 / 94.5 157.0 / 127.0 139.6 / 109.5
Declared EER
DC,B
4.42 / 4.54 4.23 / 4.35 4.24 / 4.38
Declared Refrigerant Capacity P
C
1,3,5 kW 574.1 / 463.4 595.5 / 485.5 641.2 / 517.9
Declared Power Input D
C
kW 100.4 / 78.6 105.6 / 83.9 116.8 / 91.3
Declared EER
DC,C
5.72 / 5.89 5.64 / 5.79 5.49 / 5.68
Declared Refrigerant Capacity P
D
1,3,5 kW 475.7 / 356.1 499.0 / 367.2 534.9 / 400.3
Declared Power Input D
D
kW 70.6 / 53.5 74.7 / 55.4 80.6 / 61.2
Declared EER
DC,D
6.74 / 6.66 6.68 / 6.63 6.64 / 6.54
SSCEE
2,3,5 % 179.5 179.3 171.7
SSCEE Tier
6 Tier 2 (2021) Tier 2 (2021) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 570.6 596.3 632.5
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 568.1 594.1 629.1
Declared EER
d
35°C
3.19 3.11 3.05
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 532.4 / 429.1 664.8 / 553.0 592.7 / 479.4
Declared EER
d
30°C
4.42 / 4.54 4.23 / 4.35 4.24 / 4.38
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 574.1 / 463.4 595.5 / 485.5 641.2 / 517.9
Declared EER
d
25°C
5.72 / 5.89 5.64 / 5.79 5.49 / 5.68
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.7 / 356.1 499.0 / 367.2 534.9 / 400.3
Declared EER
d
20°C
6.74 / 6.66 6.68 / 6.63 6.64 / 6.54
Sound Power Level LWA
dB(A) 88 89 89
Air ow rate
m³/h 254286 254286 254286
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.950 2.701 4.047
Standby Mode P
SB
kW 0.311 0.311 0.311
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
264
Chiller Technical Manual 7267818 V1.13.0_01_2018