Notes: Units DCF058DR-11DYV0 DCF060DR-12DVV0 DCF065DR-12FVW0
SEPR
1,3,5 6.05 6.13 6.11
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 653393 668758 723601
Rated Refrigerant Capacity
P
A
1,3,5 kW 533.2 553.4 596.7
Rated Power Input D
A
kW 189.1 192.8 209.4
Rated EER
DC,A
2.82 2.87 2.85
Declared Refrigerant Capacity P
B
1,3,5 kW 594.4 / 495.3 518.2 / 419.0 666.3 / 554.3
Declared Power Input D
B
kW 155.9 / 127.2 129.7 / 101.0 172.9 / 139.0
Declared EER
DC,B
3.81 / 3.89 4.00 / 4.15 3.85 / 3.99
Declared Refrigerant Capacity P
C
1,3,5 kW 536.7 / 438.3 561.3 / 454.3 601.6 / 492.2
Declared Power Input D
C
kW 106.6 / 82.8 108.3 / 84.2 116.5 / 92.1
Declared EER
DC,C
5.04 / 5.29 5.18 / 5.40 5.17 / 5.34
Declared Refrigerant Capacity P
D
1,3,5 kW 423.5 / 341.8 439.6 / 356.4 473.4 / 381.5
Declared Power Input D
D
kW 49.2 / 53.1 51.1 / 54.8 54.9 / 58.3
Declared EER
DC,D
8.61 / 6.43 8.60 / 6.51 8.62 / 6.55
SSCEE
2,3,5 % 161.4 164.5 161.9
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 536.2 556.5 600.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 533.2 553.4 596.7
Declared EER
d
35°C
2.82 2.87 2.85
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 594.4 / 495.3 518.2 / 419.0 666.3 / 554.3
Declared EER
d
30°C
3.81 / 3.89 4.00 / 4.15 3.85 / 3.99
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 536.7 / 438.3 561.3 / 454.3 601.6 / 492.2
Declared EER
d
25°C
5.04 / 5.29 5.18 / 5.40 5.17 / 5.34
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 423.5 / 341.8 439.6 / 356.4 473.4 / 381.5
Declared EER
d
20°C
8.61 / 6.43 8.60 / 6.51 8.62 / 6.55
Sound Power Level LWA
dB(A) 92 92 93
Air ow rate
m³/h 232768 253929 253929
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 3.488 3.639 4.603
Standby Mode P
SB
kW 0.286 0.291 0.291
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF058DR-11DYV0, DCF060DR-12DVV0, DCF065DR-12FVW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections