Technical Data
Ecodesign
DCC068TX-16GPPY, DCC072TX-17GPYY, DCC077TX-18GYYY
Notes: Units DCC068TX-16GPPY DCC072TX-17GPYY DCC077TX-18GYYY
SEPR
1,3,5 5.64 5.61 5.63
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 880382 934199 1000806
Rated Refrigerant Capacity
P
A
1,3,5 kW 669.7 707.2 761
Rated Power Input D
A
kW 225.5 240.5 259.7
Rated EER
DC,A
2.97 2.94 2.93
Declared Refrigerant Capacity P
B
1,3,5 kW 665.0 / 570.9 705.7 / 617.4 766.2 / 676.3
Declared Power Input D
B
kW 160.0 / 136.3 172.8 / 147.3 188.3 / 162.6
Declared EER
DC,B
4.16 / 4.19 4.08 / 4.19 4.07 / 4.16
Declared Refrigerant Capacity P
C
1,3,5 kW 621.5 / 496.2 667.7 / 567.1 732.9 / 633.3
Declared Power Input D
C
kW 114.3 / 88.7 122.8 / 103.0 135.9 / 114.0
Declared EER
DC,C
5.44 / 5.59 5.44 / 5.51 5.39 / 5.55
Declared Refrigerant Capacity P
D
1,3,5 kW 654.4 / 516.9 591.0 / 484.4 658.2 / 548.1
Declared Power Input D
D
kW 98.8 / 78.1 89.8 / 73.7 99.2 / 83.0
Declared EER
DC,D
6.62 / 6.62 6.58 / 6.57 6.63 / 6.60
SSCEE
2,3,5 % 169.1 172.1 173.1
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 672.6 709.1 763.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 669.7 707.2 761
Declared EER
d
35°C
2.97 2.94 2.93
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 665.0 / 570.9 705.7 / 617.4 766.2 / 676.3
Declared EER
d
30°C
4.16 / 4.19 4.08 / 4.19 4.07 / 4.16
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 621.5 / 496.2 667.7 / 567.1 732.9 / 633.3
Declared EER
d
25°C
5.44 / 5.59 5.44 / 5.51 5.39 / 5.55
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 654.4 / 516.9 591.0 / 484.4 658.2 / 548.1
Declared EER
d
20°C
6.62 / 6.62 6.58 / 6.57 6.63 / 6.60
Sound Power Level LWA
dB(A) 89 89 88
Air ow rate
m³/h 254286 270179 286072
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.605 2.422 3.135
Standby Mode P
SB
kW 0.335 0.351 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections