Technical Data
Ecodesign
DCC070TX-19GPPY, DCC074TX-20GPYY
Notes: Units DCC070TX-19GPPY DCC074TX-20GPYY
SEPR
1,3,5 5.81 5.75
SEPR Tier
Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 876915 933428
Rated Refrigerant Capacity
P
A
1,3,5 kW 687.3 724.3
Rated Power Input D
A
kW 218.9 234.4
Rated EER
DC,A
3.14 3.09
Declared Refrigerant Capacity P
B
1,3,5 kW 677.2 / 582.0 717.4 / 625.6
Declared Power Input D
B
kW 155.9 / 132.8 168.8 / 144.0
Declared EER
DC,B
4.34 / 4.38 4.25 / 4.34
Declared Refrigerant Capacity P
C
1,3,5 kW 628.7 / 501.3 674.0 / 572.4
Declared Power Input D
C
kW 110.8 / 86.4 119.6 / 100.4
Declared EER
DC,C
5.67 / 5.80 5.64 / 5.70
Declared Refrigerant Capacity P
D
1,3,5 kW 654.5 / 516.9 590.9 / 484.4
Declared Power Input D
D
kW 97.0 / 77.2 89.0 / 72.9
Declared EER
DC,D
6.75 / 6.70 6.64 / 6.64
SSCEE
2,3,5 % 175.7 177.0
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 690.2 726.4
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 687.3 724.3
Declared EER
d
35°C
3.14 3.09
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 677.2 / 582.0 717.4 / 625.6
Declared EER
d
30°C
4.34 / 4.38 4.25 / 4.34
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 628.7 / 501.3 674.0 / 572.4
Declared EER
d
25°C
5.67 / 5.80 5.64 / 5.70
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 654.5 / 516.9 590.9 / 484.4
Declared EER
d
20°C
6.75 / 6.70 6.64 / 6.64
Sound Power Level LWA
dB(A) 89 89
Air ow rate
m³/h 301965 317858
Off mode P
OFF
kW 0.169 0.169
Thermostat-off mode P
TO
kW 3.295 2.587
Standby Mode P
SB
kW 0.350 0.366
Crankcase heater mode P
CK
kW 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections