EasyManua.ls Logo

AIREDALE DeltaChill - Dcf051 Dr-09 Dpy0, Dcf053 Dr-10 Dpv0, Dcf055 Dr-10 Dyy0

AIREDALE DeltaChill
302 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Notes: Units DCF051DR-09DPY0 DCF053DR-10DPV0 DCF055DR-10DYY0
SEPR
1,3,5 5.87 5.91 5.92
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 595359 616597 641173
Rated Refrigerant Capacity
P
A
1,3,5 kW 471.9 492.2 512.3
Rated Power Input D
A
kW 169.1 172.7 186.3
Rated EER
DC,A
2.79 2.85 2.75
Declared Refrigerant Capacity P
B
1,3,5 kW 526.9 / 435.1 550.0 / 450.0 479.8 / 388.7
Declared Power Input D
B
kW 140.1 / 111.9 142.6 / 113.8 126.0 / 97.9
Declared EER
DC,B
3.76 / 3.89 3.86 / 3.95 3.81 / 3.97
Declared Refrigerant Capacity P
C
1,3,5 kW 472.6 / 369.0 488.7 / 376.8 520.1 / 421.6
Declared Power Input D
C
kW 94.1 / 72.8 95.6 / 73.7 105.8 / 82.0
Declared EER
DC,C
5.02 / 5.07 5.11 / 5.11 4.92 / 5.14
Declared Refrigerant Capacity P
D
1,3,5 kW 373.8 / 253.2 389.9 / 260.4 406.3 / 333.9
Declared Power Input D
D
kW 45.1 / 39.5 47.2 / 40.7 47.8 / 52.7
Declared EER
DC,D
8.30 / 6.41 8.27 / 6.40 8.50 / 6.34
SSCEE
2,3,5 % 153.3 154.3 156.2
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
Technical Data
Ecodesign
DCF051DR-09DPY0, DCF053DR-10DPV0, DCF055DR-10DYY0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
273
Chiller Technical Manual 7267818 V1.13.0_01_2018
Technic al

Table of Contents

Related product manuals