Technical Data
Ecodesign
DCC031DR-08BLM0, DCC032DR-06BMM0, DCC033DR-08BMM0
Notes: Units DCC068TR-13GPPY DCC072TR-14GPYY DCC077TR-15GYYY
SEPR
1,3,5 5.36 5.35 5.46
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 932791 986504 1043569
Rated Refrigerant Capacity
P
A
1,3,5 kW 674.6 712.7 769
Rated Power Input D
A
kW 235.1 251.0 269.8
Rated EER
DC,A
2.87 2.84 2.85
Declared Refrigerant Capacity P
B
1,3,5 kW 658.9 / 566.1 700.1 / 611.2 762.0 / 671.0
Declared Power Input D
B
kW 166.8 / 142.2 179.8 / 152.8 195.3 / 168.1
Declared EER
DC,B
3.95 / 3.98 3.89 / 4.00 3.90 / 3.99
Declared Refrigerant Capacity P
C
1,3,5 kW 611.7 / 489.4 658.7 / 559.6 723.9 / 626.3
Declared Power Input D
C
kW 119.2 / 92.1 127.6 / 107.1 140.6 / 117.6
Declared EER
DC,C
5.13 / 5.32 5.16 / 5.23 5.15 / 5.33
Declared Refrigerant Capacity P
D
1,3,5 kW 644.9 / 512.1 586.2 / 479.6 658.1 / 548.0
Declared Power Input D
D
kW 103.2 / 80.4 92.6 / 76.2 100.3 / 83.7
Declared EER
DC,D
6.25 / 6.37 6.33 / 6.30 6.56 / 6.54
SSCEE
2,3,5 % 162.6 164.9 167.7
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 677.5 715 771.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 674.6 712.7 769
Declared EER
d
35°C
2.87 2.84 2.85
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 658.9 / 566.1 700.1 / 611.2 762.0 / 671.0
Declared EER
d
30°C
3.95 / 3.98 3.89 / 4.00 3.90 / 3.99
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 611.7 / 489.4 658.7 / 559.6 723.9 / 626.3
Declared EER
d
25°C
5.13 / 5.32 5.16 / 5.23 5.15 / 5.33
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 644.9 / 512.1 586.2 / 479.6 658.1 / 548.0
Declared EER
d
20°C
6.25 / 6.37 6.33 / 6.30 6.56 / 6.54
Sound Power Level LWA
dB(A) 94 94 94
Air ow rate
m³/h 301592 324791 347991
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.615 3.047 3.195
Standby Mode P
SB
kW 0.320 0.336 0.353
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections