Technical Data
Ecodesign
DCC066TX-13GPPY, DCC070TX-14GPYY, DCC075TX-15GYYY
Notes: Units DCC066TX-13GPPY DCC070TX-14GPYY DCC075TX-15GYYY
SEPR 1,3,5 5.37 5.35 5.47
SEPR Tier Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Annual Electricity Consumption kWh/a 888943 944007 996551
Rated Refrigerant Capacity
P
A
1,3,5 kW 644 682.1 735.3
Rated Power Input D
A
kW 235.9 251.7 270.3
Rated EER
DC,A
2.73 2.71 2.72
Declared Refrigerant Capacity P
B
1,3,5 kW 647.2 / 554.4 688.7 / 605.5 748.7 / 664.4
Declared Power Input D
B
kW 166.6 / 142.0 179.8 / 152.7 195.4 / 168.2
Declared EER
DC,B
3.88 / 3.90 3.83 / 3.97 3.83 / 3.95
Declared Refrigerant Capacity P
C
1,3,5 kW 607.9 / 487.7 656.7 / 557.7 721.7 / 626.0
Declared Power Input D
C
kW 118.7 / 91.6 127.2 / 106.7 140.5 / 117.5
Declared EER
DC,C
5.12 / 5.32 5.16 / 5.23 5.14 / 5.33
Declared Refrigerant Capacity P
D
1,3,5 kW 645.3 / 512.5 586.5 / 479.9 658.1 / 548.0
Declared Power Input D
D
kW 102.9 / 80.1 92.4 / 76.0 100.3 / 83.8
Declared EER
DC,D
6.27 / 6.40 6.35 / 6.32 6.56 / 6.54
SSCEE 2,3,5 % 161.7 163.7 166.6
SSCEE Tier 6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 646.6 684.2 738
Declared Cooling Capacity 35°C Pdc 2,3,5 kW 644 682.1 735.3
Declared EER
d
35°C 2.73 2.71 2.72
Declared Cooling Capacity 30°C Pdc 2,3,5 kW 647.2 / 554.4 688.7 / 605.5 748.7 / 664.4
Declared EER
d
30°C 3.88 / 3.90 3.83 / 3.97 3.83 / 3.95
Declared Cooling Capacity 25°C Pdc 2,3,5 kW 607.9 / 487.7 656.7 / 557.7 721.7 / 626.0
Declared EER
d
25°C 5.12 / 5.32 5.16 / 5.23 5.14 / 5.33
Declared Cooling Capacity 20°C Pdc 2,3,5 kW 645.3 / 512.5 586.5 / 479.9 658.1 / 548.0
Declared EER
d
20°C 6.27 / 6.40 6.35 / 6.32 6.56 / 6.54
Sound Power Level LWA dB(A) 89 88 88
Air ow rate m³/h 206608 222501 238393
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.231 2.739 3.579
Standby Mode P
SB
kW 0.320 0.336 0.353
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections