Technical Data
Ecodesign
DCC086TX-18GVVW, DCC088TX-18GVWW, DCC091TX-18GWWW
Notes: Units DCC086TX-18GVVW DCC088TX-18GVWW DCC091TX-18GWWW
SEPR
1,3,5 5.67 5.60 5.53
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1091160 1138392 1188422
Rated Refrigerant Capacity
P
A
1,3,5 kW 835.1 861.1 887.1
Rated Power Input D
A
kW 294.0 309.7 324.9
Rated EER
DC,A
2.84 2.78 2.73
Declared Refrigerant Capacity P
B
1,3,5 kW 843.9 / 749.1 874.0 / 772.2 904.2 / 802.4
Declared Power Input D
B
kW 208.6 / 180.9 221.2 / 188.5 233.9 / 201.2
Declared EER
DC,B
4.05 / 4.14 3.95 / 4.10 3.87 / 3.99
Declared Refrigerant Capacity P
C
1,3,5 kW 813.6 / 707.1 837.9 / 731.4 871.4 / 755.7
Declared Power Input D
C
kW 150.9 / 127.5 157.2 / 133.9 167.6 / 140.2
Declared EER
DC,C
5.39 / 5.54 5.33 / 5.46 5.20 / 5.39
Declared Refrigerant Capacity P
D
1,3,5 kW 739.4 / 606.8 766.3 / 633.7 793.1 / 660.5
Declared Power Input D
D
kW 109.9 / 90.1 114.7 / 94.9 119.5 / 99.7
Declared EER
DC,D
6.73 / 6.74 6.68 / 6.68 6.63 / 6.62
SSCEE
2,3,5 % 175.4 173.1 17%.2
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 837.3 863.5 889.6
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 835.1 861.1 887.1
Declared EER
d
35°C
2.84 2.78 2.73
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 843.9 / 749.1 874.0 / 772.2 904.2 / 802.4
Declared EER
d
30°C
4.05 / 4.14 3.95 / 4.10 3.87 / 3.99
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 813.6 / 707.1 837.9 / 731.4 871.4 / 755.7
Declared EER
d
25°C
5.39 / 5.54 5.33 / 5.46 5.20 / 5.39
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 739.4 / 606.8 766.3 / 633.7 793.1 / 660.5
Declared EER
d
20°C
6.73 / 6.74 6.68 / 6.68 6.63 / 6.62
Sound Power Level LWA
dB(A) 90 91 91
Air ow rate
m³/h 286072 286072 286072
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 2.877 3.099 3.331
Standby Mode P
SB
kW 0.368 0.368 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections