Technical Data
Ecodesign
DCF062DR-10FVW0, DCF065DR-10FWW0, DCF069TR-10GPPY
Notes: Units DCF062DR-10FVW0 DCF065DR-10FWW0 DCF069TR-10GPPY
SEPR
1,3,5 5.89 5.73 5.35
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 1 (2018)
Annual Electricity Consumption
kWh/a 729427 784490 886854
Rated Refrigerant Capacity
P
A
1,3,5 kW 580.1 607.2 640.1
Rated Power Input D
A
kW 216.5 231.8 254.0
Rated EER
DC,A
2.68 2.62 2.52
Declared Refrigerant Capacity P
B
1,3,5 kW 545.9 / 446.9 579.8 / 470.4 641.6 / 549.9
Declared Power Input D
B
kW 144.2 / 113.7 158.0 / 122.3 182.4 / 155.8
Declared EER
DC,B
3.79 / 3.93 3.67 / 3.85 3.52 / 3.53
Declared Refrigerant Capacity P
C
1,3,5 kW 592.5 / 485.5 628.8 / 510.8 601.6 / 483.1
Declared Power Input D
C
kW 121.0 / 95.4 132.9 / 102.6 132.0 / 101.5
Declared EER
DC,C
4.89 / 5.09 4.73 / 4.98 4.56 / 4.76
Declared Refrigerant Capacity P
D
1,3,5 kW 460.0 / 381.5 481.2 / 408.5 507.4 / 511.4
Declared Power Input D
D
kW 54.3 / 59.3 58.6 / 65.6 67.6 / 87.6
Declared EER
DC,D
8.48 / 6.43 8.21 / 6.23 7.50 / 5.84
SSCEE
2,3,5 % 155.6 151.3 142.1
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections