Notes: Units DCF062DR-14DVV0 DCF066DR-14FVW0 DCF070DR-14FWW0
SEPR
1,3,5 6.25 6.26 6.17
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 665088 715692 764999
Rated Refrigerant Capacity
P
A
1,3,5 kW 560.8 604.7 636.8
Rated Power Input D
A
kW 186.9 203.6 218.1
Rated EER
DC,A
3 2.97 2.92
Declared Refrigerant Capacity P
B
1,3,5 kW 523.9 / 423.0 675.0 / 560.8 596.5 / 482.3
Declared Power Input D
B
kW 126.1 / 98.5 167.6 / 135.1 147.6 / 115.1
Declared EER
DC,B
4.16 / 4.29 4.03 / 4.15 4.04 / 4.19
Declared Refrigerant Capacity P
C
1,3,5 kW 567.5 / 458.6 608.7 / 497.3 646.9 / 523.6
Declared Power Input D
C
kW 105.1 / 82.0 113.0 / 89.7 123.6 / 96.2
Declared EER
DC,C
5.40 / 5.59 5.39 / 5.54 5.23 / 5.44
Declared Refrigerant Capacity P
D
1,3,5 kW 445.7 / 356.4 479.9 / 381.7 505.3 / 410.9
Declared Power Input D
D
kW 52.4 / 54.4 55.6 / 57.8 58.8 / 62.8
Declared EER
DC,D
8.51 / 6.55 8.62 / 6.61 8.60 / 6.54
SSCEE
2,3,5 % 169.5 167.1 163.8
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 563.8 608.5 641
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 560.8 604.7 636.8
Declared EER
d
35°C
3 2.97 2.92
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 523.9 / 423.0 675.0 / 560.8 596.5 / 482.3
Declared EER
d
30°C
4.16 / 4.29 4.03 / 4.15 4.04 / 4.19
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 567.5 / 458.6 608.7 / 497.3 646.9 / 523.6
Declared EER
d
25°C
5.40 / 5.59 5.39 / 5.54 5.23 / 5.44
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 445.7 / 356.4 479.9 / 381.7 505.3 / 410.9
Declared EER
d
20°C
8.51 / 6.55 8.62 / 6.61 8.60 / 6.54
Sound Power Level LWA
dB(A) 91 93 93
Air ow rate
m³/h 296251 296251 296251
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 3.520 4.473 4.671
Standby Mode P
SB
kW 0.301 0.301 0.301
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
Technical Data
Ecodesign
DCF062DR-14DVV0, DCF066DR-14FVW0, DCF070DR-14FWW0
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
Introduction
DeltaChill™ Air Cooled and FreeCool
280
Chiller Technical Manual 7267818 V1.13.0_01_2018
Technic al

Table of Contents

Related product manuals