Technical Data
Ecodesign
DCC049DR-10EPV0, DCC051DR-10EYY0, DCC054DR-11DYV0
Notes: Units DCC049DR-10EPV0 DCC051DR-10EYY0 DCC054DR-11DYV0
SEPR
1,3,5 5.36 5.32 5.56
SEPR Tier
Tier 1 (2018) Tier 1 (2018) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 664864 701245 713403
Rated Refrigerant Capacity
P
A
1,3,5 kW 480.7 503.4 535
Rated Power Input D
A
kW 165.8 179.1 183.2
Rated EER
DC,A
2.9 2.81 2.92
Declared Refrigerant Capacity P
B
1,3,5 kW 532.7 / 436.2 556.1 / 467.1 593.0 / 494.1
Declared Power Input D
B
kW 135.9 / 108.3 147.8 / 120.8 150.5 / 122.7
Declared EER
DC,B
3.92 / 4.03 3.76 / 3.87 3.94 / 4.03
Declared Refrigerant Capacity P
C
1,3,5 kW 469.8 / 363.2 502.1 / 406.4 532.0 / 434.0
Declared Power Input D
C
kW 90.4 / 69.4 101.0 / 78.1 102.5 / 79.5
Declared EER
DC,C
5.19 / 5.23 4.97 / 5.20 5.19 / 5.46
Declared Refrigerant Capacity P
D
1,3,5 kW 492.7 / 380.1 424.7 / 318.0 453.3 / 336.2
Declared Power Input D
D
kW 77.9 / 60.8 66.7 / 50.4 68.3 / 51.1
Declared EER
DC,D
6.32 / 6.25 6.36 / 6.31 6.63 / 6.58
SSCEE
2,3,5 % 164.3 163.3 172.0
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 482.6 505.5 536.5
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 480.7 503.4 535
Declared EER
d
35°C
2.9 2.81 2.92
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 532.7 / 436.2 556.1 / 467.1 593.0 / 494.1
Declared EER
d
30°C
3.92 / 4.03 3.76 / 3.87 3.94 / 4.03
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 469.8 / 363.2 502.1 / 406.4 532.0 / 434.0
Declared EER
d
25°C
5.19 / 5.23 4.97 / 5.20 5.19 / 5.46
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 492.7 / 380.1 424.7 / 318.0 453.3 / 336.2
Declared EER
d
20°C
6.32 / 6.25 6.36 / 6.31 6.63 / 6.58
Sound Power Level LWA
dB(A) 92 92 92
Air ow rate
m³/h 231994 231994 255193
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.256 2.522 1.932
Standby Mode P
SB
kW 0.269 0.281 0.286
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections