Technical Data
Ecodesign
DCC088TR-18GVVW, DCC091TR-18GVWW, DCC094TR-18GWWW
Notes: Units DCC088TR-18GVVW DCC091TR-18GVWW DCC094TR-18GWWW
SEPR
1,3,5 5.65 5.58 5.51
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 1136954 1191901 1249763
Rated Refrigerant Capacity
P
A
1,3,5 kW 866.8 897.8 928.9
Rated Power Input D
A
kW 294.8 309.6 324.8
Rated EER
DC,A
2.94 2.9 2.86
Declared Refrigerant Capacity P
B
1,3,5 kW 853.1 / 753.6 886.5 / 776.7 919.8 / 810.0
Declared Power Input D
B
kW 209.3 / 181.4 221.6 / 189.0 233.9 / 201.4
Declared EER
DC,B
4.08 / 4.15 4.00 / 4.11 3.93 / 4.02
Declared Refrigerant Capacity P
C
1,3,5 kW 814.0 / 707.0 838.3 / 731.3 873.7 / 755.7
Declared Power Input D
C
kW 151.2 / 127.8 157.6 / 134.1 168.1 / 140.5
Declared EER
DC,C
5.38 / 5.53 5.32 / 5.45 5.20 / 5.38
Declared Refrigerant Capacity P
D
1,3,5 kW 739.2 / 606.6 766.0 / 633.4 792.8 / 660.2
Declared Power Input D
D
kW 110.1 / 90.3 114.9 / 95.1 119.8 / 100.0
Declared EER
DC,D
6.72 / 6.72 6.66 / 6.66 6.62 / 6.60
SSCEE
2,3,5 % 174.9 172.6 169.6
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 869.2 900.5 931.7
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 866.8 897.8 928.9
Declared EER
d
35°C
2.94 2.9 2.86
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 853.1 / 753.6 886.5 / 776.7 919.8 / 810.0
Declared EER
d
30°C
4.08 / 4.15 4.00 / 4.11 3.93 / 4.02
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 814.0 / 707.0 838.3 / 731.3 873.7 / 755.7
Declared EER
d
25°C
5.38 / 5.53 5.32 / 5.45 5.20 / 5.38
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 739.2 / 606.6 766.0 / 633.4 792.8 / 660.2
Declared EER
d
20°C
6.72 / 6.72 6.66 / 6.66 6.62 / 6.60
Sound Power Level LWA
dB(A) 94 95 96
Air ow rate
m³/h 417589 417589 417589
Off mode P
OFF
kW 0.169 0.169 0.169
Thermostat-off mode P
TO
kW 3.149 3.430 3.726
Standby Mode P
SB
kW 0.368 0.368 0.368
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections