Technical Data
Ecodesign
DCC057DX-14DVV0, DCC060DX-14DVW0, DCC063DX-14DWW0
Notes: Units DCC057DX-14DVV0 DCC060DX-14DVW0 DCC063DX-14DWW0
SEPR
1,3,5 5.80 5.72 5.62
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 712489 754488 811319
Rated Refrigerant Capacity
P
A
1,3,5 kW 557.4 582.2 615.6
Rated Power Input D
A
kW 181.6 195.4 210.8
Rated EER
DC,A
3.07 2.98 2.92
Declared Refrigerant Capacity P
B
1,3,5 kW 526.2 / 426.0 546.8 / 447.1 585.2 / 476.4
Declared Power Input D
B
kW 122.6 / 96.0 129.4 / 102.8 142.6 / 111.5
Declared EER
DC,B
4.29 / 4.44 4.23 / 4.35 4.10 / 4.27
Declared Refrigerant Capacity P
C
1,3,5 kW 569.7 / 460.3 591.0 / 482.2 635.7 / 514.3
Declared Power Input D
C
kW 102.5 / 80.0 108.0 / 85.5 119.4 / 93.0
Declared EER
DC,C
5.56 / 5.76 5.47 / 5.64 5.32 / 5.53
Declared Refrigerant Capacity P
D
1,3,5 kW 475.8 / 356.2 499.2 / 367.4 535.0 / 400.5
Declared Power Input D
D
kW 70.7 / 53.5 74.8 / 55.3 80.7 / 61.2
Declared EER
DC,D
6.73 / 6.66 6.68 / 6.64 6.63 / 6.55
SSCEE
2,3,5 % 176.6 176.3 168.9
SSCEE Tier
6 Tier 1 (2018) Tier 1 (2018) Tier 1 (2018)
Rated Cooling Capacity P
rated,c
2,4,5 559.7 584.3 618.8
Declared Cooling Capacity 35°C Pdc
2,3,5 kW 557.4 582.2 615.6
Declared EER
d
35°C
3.07 2.98 2.92
Declared Cooling Capacity 30°C Pdc
2,3,5 kW 526.2 / 426.0 546.8 / 447.1 585.2 / 476.4
Declared EER
d
30°C
4.29 / 4.44 4.23 / 4.35 4.10 / 4.27
Declared Cooling Capacity 25°C Pdc
2,3,5 kW 569.7 / 460.3 591.0 / 482.2 635.7 / 514.3
Declared EER
d
25°C
5.56 / 5.76 5.47 / 5.64 5.32 / 5.53
Declared Cooling Capacity 20°C Pdc
2,3,5 kW 475.8 / 356.2 499.2 / 367.4 535.0 / 400.5
Declared EER
d
20°C
6.73 / 6.66 6.68 / 6.64 6.63 / 6.55
Sound Power Level LWA
dB(A) 88 89 89
Air ow rate
m³/h 222501 222501 222501
Off mode P
OFF
kW 0.157 0.157 0.157
Thermostat-off mode P
TO
kW 2.786 2.537 3.797
Standby Mode P
SB
kW 0.301 0.301 0.301
Crankcase heater mode P
CK
kW 0.000 0.000 0.000
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections