Notes: Units DCF075TX-14GPYY DCF079TX-15GYYY DCF082TX-16HYYV
SEPR
1,3,5 6.04 6.06 6.15
SEPR Tier
Tier 2 (2021) Tier 2 (2021) Tier 2 (2021)
Annual Electricity Consumption
kWh/a 844200 892777 908931
Rated Refrigerant Capacity
P
A
1,3,5 kW 688.2 730.7 754.7
Rated Power Input D
A
kW 261.7 280.0 282.7
Rated EER
DC,A
2.63 2.61 2.67
Declared Refrigerant Capacity P
B
1,3,5 kW 702.4 / 619.3 749.5 / 666.5 764.4 / 681.2
Declared Power Input D
B
kW 188.3 / 159.9 203.3 / 174.9 204.5 / 176.1
Declared EER
DC,B
3.73 / 3.87 3.69 / 3.81 3.74 / 3.87
Declared Refrigerant Capacity P
C
1,3,5 kW 678.2 / 575.2 633.9 / 530.9 742.7 / 647.7
Declared Power Input D
C
kW 134.0 / 112.7 122.9 / 101.6 147.2 / 123.5
Declared EER
DC,C
5.06 / 5.10 5.16 / 5.23 5.05 / 5.24
Declared Refrigerant Capacity P
D
1,3,5 kW 546.0 / 498.7 579.4 / 558.5 599.2 / 562.6
Declared Power Input D
D
kW 61.0 / 80.3 64.4 / 87.5 65.6 / 87.7
Declared EER
DC,D
8.95 / 6.21 8.99 / 6.39 9.14 / 6.41
SSCEE
2,3,5 % 154.9 154.8 158.1
SSCEE Tier
6 Not Compliant Not Compliant Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5 n/a n/a n/a
Declared Cooling Capacity 35°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
35°C
n/a n/a n/a
Declared Cooling Capacity 30°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
30°C
n/a n/a n/a
Declared Cooling Capacity 25°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
25°C
n/a n/a n/a
Declared Cooling Capacity 20°C Pdc
2,3,5 kW n/a n/a n/a
Declared EER
d
20°C
n/a n/a n/a
Sound Power Level LWA
dB(A) n/a n/a n/a
Air ow rate
m³/h n/a n/a n/a
Off mode P
OFF
kW n/a n/a n/a
Thermostat-off mode P
TO
kW n/a n/a n/a
Standby Mode P
SB
kW n/a n/a n/a
Crankcase heater mode P
CK
kW n/a n/a n/a
Technical Data
Ecodesign
DCF075TX-14GPYY, DCF079TX-15GYYY, DCF082TX-16HYYV
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside conguration.
(6)
Please contact Airedale regarding Non Compliant selections
Chillers
DeltaChill™ Air Cooled and FreeCool
Introduction
287
Chiller Technical Manual 7267818 V1.13.0_01_2018